Chapter 3 Operation
z
z
06: Bypass enable/ disable when the UPS is off
Parameter 3:
Enable or disable bypass function. You may choose the following
two options.
ENA:
Bypass enable
DIS:
Bypass disable (Default)
z
z
07: Bypass voltage range setting
Parameter 2 & 3:
Set the acceptable high voltage point and acceptable low
voltage point for bypass mode by pressing the Down key or Up key.
HLS:
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to
264Vac. (Default: 264Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from 170Vac to
220Vac. (Default: 170Vac)