DVP-01HC 

High-speed Counter 

Module 

Instruction Sheet 

 

1  

WARNING 

 

  Please carefully read this instruction thoroughly prior to use the DVP-01HC. 

  Make sure that power is OFF before wiring.   

  This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne 

dust, humidity, electric shock risk and vibration. Also, it is equipped with protective methods 
such as some special tools or keys to open the enclosure, in order to prevent hazard to users 
or damage the PLC.   

  Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it 

may damage the PLC. Check all the wiring prior to power up.   

 

 

INTRODUCTION 

 

2.1 

Model Name Explanation and Peripherals 

 

Thank you for choosing DELTA’s PLC DVP series. DVP-01HC high-speed counter input 

module could accept 200KHz pulse from external counter. It uses instruction FROM/TO to 
read/write the data in module via EH MPU. There are 33 Controlled Registers (CR, each 
register is 16-bit)

 

in each module. 32 bits data consists of two continuous CRs and allow 

executing itself after setting CR.   

 

The different counter modes, such as single-phase mode, two phases mode, 16-bit mode or 

32-bit mode, can be designated by CR. The controlled registers are written by instruction TO 
via MPU. When wiring, connect 24V, A24+, B24+, P24+, D24+, A12+, B12+, A5+, B5+, P5+ 
and D5+ to positive potential. In the same way, 0V, A24-, B24-, P24-, D24-, A12-, B12-, A5-, 
B5-, P5- and D5- should be connected to negative potential.   

 

Input signal source could be 1-phase or 2-phase encoder and voltage level could be 5V, 12V 

and 24V. Besides, it also provides two terminals, PRESET and DISABLE. When terminal 
“PRE” is on, the data in CR#10 and CR#11 will be sent to CR#20 and CR#21. That also means 
current value of counter will be changed to be factory setting. When terminal “DIS” is on, 
“count” operation is disabled.   

 

There are two outputs, YH0 and YH1, in hardware input module of DVP-01HC. When counter 

value is equal to the setting, the corresponding output point will activate. The transistors of 
output points are independent and isolated. 

 

Nameplate Explanation

 

24VDC 3W MAX.

0.5 A  5VDC~30VDC  1~10KHz

01HC-H0T4350001

VX.XX

5VDC 12VDC  24

   1~200KHz

VDC

Input power supply spec.

Output module spec.

Barcode, serial number and version

Model Name

Input spec.

 

 

Model and Serial Number Explanation

 

Serial Number

Model

for EH series MPU 

Product Series

Channel number 

Model type

Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model

序號

HC: High-speed counter module

 

2.2 

Product Profile and Outline 

1

2

3

4

7

7

5

3

6

10

8

9

 

Unit: mm 

1. DIN rail track (35mm) 

2. Mounting wire to connect extension module/extension unit

3. Model name 

4. Status Indicator (Power, Run and ERROR) 

5. DIN rail clip 

6. Terminal 

7. Mounting hole 

8. Terminal layout 

9. Extension port to connect extension module/unit 10. RS-485 communication port 

 

 

LED Display 

1.  Power   

: Power LED. When ex24V power is applied, it will be ON. 

2.  L.V. 

: Low voltage LED. When external power supply is lower than 19V, it will be ON. 

3.  UP   

: Count up LED 

4.  DOWN   

: Count down LED 

5. 

ψ

A   

: When input point A is ON, it will light. 

6. 

ψ

B   

: When input point B is ON, it will light. 

7.  PRE 

: PRESET LED. When external terminal PRE is ON, it will light.   

8.  DIS   

: DISABLE LED. When external terminal DIS is ON, it will light. 

9.  YH0, YH1    : When output points YH0 and YH1 are ON, it will light. 

2.3

 

Wiring

 

To suit M3.5 screw terminals

Below 6.2

Below 6.2

1. Please use O-type or Y-type terminals for I/O wiring terminals. The 

specification for the terminals is as shown on the left. Tighten PLC 
terminal screws to a torque of 5 to 8 kg-cm (4.3~6.9 in-lbs).   

2. I/O signal wires or power supply should not run through the same 

multi-wire cable or conduit.   

3.  Use copper conductor only, 60

.  

 

External Wiring 

4.7K

Shielded wire

A24+

OA

A12+

A5+

A -

B24+
B12+

B5+

B -

2.2K

0.68K

4.7K

2.2K

0.68K

P+24

P+5

PRE-

D+24

D+5

DIS-

4.7K

4.7K

0.68K

4.7K

4.7K

0.68K

OB

PRESET

DISABLE

START

EH MPU

connection 
wire

YH0+

YH0-

YH1+

YH1-

+24V

0V

Filter

DC/DC

+24V

+5V

0V

+24V

External Power

DC 12V to 24V

01HC High-speed Counter Module

OUT

OUT

OUT

A phase

B phase

Z phase

+24V

COME

0V

+24V

External Power

DC5V, 12V, 24V

PNP  output encoder

Shielded wire

Shielded wire

Shielded wire

 

Make sure the positive/negative pole of 01HC input terminal wiring is correct when using NPN 
encoder.  

 

Start-up current for 01HC is I

PEAK

=0.8A and general working current is I

MAX

=0.2A(input voltage 

is +24V).

 

 

3

FUNCTION SPECIFICATION

 

3.1 Function 

Specification 

1-phase Input 

2-phase (A, B) Input 

Item 

1 Input 

2 Inputs 

Normal 

Frequency 

Double 

Frequency 

Four Times 

Frequency 

Power Supply 

DC24V(-15% ~ +20%), Current consumption 140

±

30mA 

Power is supplied from PLC or external power supply. 

Max. Number of Connecting 

Units 

8 units; (All I/O points are not occupied. There can be 8 special extension units at 

most connected to EH series.) 

Voltage 

Level 

Terminals [A24+], [B24+]: DC24V 

±

10 % 

Terminals P24+], [D24+]: DC12V ~24V 

±

10 % 

Terminals [A12+], [B12+]: DC12V 

±

10 % 

Terminals [A5+], [B5+], [P5+], [D5+]: DC5V 

±

10 % 

Choose only one suitable voltage level for positive   
pole of each signal.   

A: A Phase 
B: B Phase 
P: Preset 
D: Disable 

Max. Count 

Frequency 

200KHz 200KHz 200KHz 100KHz  50KHz 

Input 

Signal 

Waveform 

t

3

t

1

t

1

t

2

t

2

t

3

t1: rise/fall time

0.8us 

t2: On/Off pulse width

2.5us 

t3: phase difference between A phase and B 
phase 

1us 

PRESET input: input pulse width

50us 

DISABLE input: input pulse width

50us 

Count Mode 

There is three count modes: count up/down ((2-phase input for AB phase), 
1-phase 2 inputs and 1-phase 1 input.) 

Range 

32-bit mode: -2,147,2,147,483,647 
16-bit mode: 0~65,536 (upper limit can be set by CR#2,3) 

Count 

Specification 

Comparison 

Method 

Two comparison values are available and correspond to two outputs, YH0 and 
YH1, respectively. When count value is equal to settings, the output will be ON. It 
adopts hardware circuit comparison and output settings with real-time handle.   

Output 

Form 

YH0+: output point YH0, transistor: Collector 
YH0-: output point YH0, transistor: Emitter 
YH1+: output point YH1, transistor: Collector 
YH1-: output point YH1, transistor: Emitter 

YH0+
YH1+

YH1-

YH0-

 

Output 

Signal 

Output 

5V TO 30VDC, 0.5A 

Connect to DVP-PLC 

MPU in Series 

The module number it connects to MPU from closest to the farthest is from 0 to 
7. 8 modules is the max and it won’t occupy any digital I/O.   

3.2 Other 

Specification

 

Environmental specifications 

Operation/Storage 

1. Operation: 0

~55

(Temperature), 50~95%(Humidity), pollution degree 2 

2. Storage: -25

~70

(Temperature), 5~95% (Humidity) 

Vibration/Shock 

immunity 

Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST 
Ea) 

Antistatic spec. 

All places between terminals and ground comply with the spec. 

 

4

CONTROLLED REGISTER (CR) 

 

DVP-01HC High-speed Counter Module 

CR No. 

HW LW

Communi

cati

on 

Address 

Latched 

Attr

ibute 

Content 

Setting Range 

#0 H415E 

 

Model type 

System used, read only, DVP-01HC model code=H’0120 

#1 H 415F 

 R/W 

Count 
up/down mode 
setting 

Setting range: 0-1, factory setting K0 
1-phase 1 input(Software): count up/down mode setting, 
count up: K0, count down:K1 

#3 #2 H 4160 

 R/W  Ring length 

16-bit: factory setting is K65,536. 

 

Example: 

M0

DTO

K0

K2

K200

K1

 

Write K200 into first extension module CR#2 and 
CR#3 (i.e. CR#3 = 0, CR #2 = 200). Setting 
range: K2 to K65,536. 

198

199

1

0

0

1

199

198

Count up

Count down

When ring length is set to K200, The count value 
will be as shown on the left. 

Count up: when count value reaches 199, the 
next count value will be 0. 

Count down: when count value reaches 0, the 
next count value will be 199. 

Setting notices: 

1.  It must write with 32-bit.   
2.  It only can be write-in when writing value is greater or equal to current count value. 
3.  It only can be set when counter stops counting and count mode is 16-bit.   