Mounting 

 

The back plate is designed for mounting directly on a standard North American, European 

or Australian electrical box, but may be mounted in other ways as well.  The back plate is 

screwed into the dry wall or electrical box and the faceplate snaps into place on top.  Use 

the hex screw located on the bottom of the housing to secure the faceplate to the back 

plate. 

 

Power (Only RTS-20Jxx) 

 

The Room Temperature Sensor with the Service Port option requires a 24 VAC @ 2VA 

power supply, typically an isolated Class 2 transformer.  More than one device – not 

including DCUs or V2 products – may be connected to the same transformer, providing the 

transformer is properly sized, including line losses, and polarity is observed between 

controllers (in regards to 24~ and GND).  The transformer must 

ONLY

 be used to provide 

power to other MS/TP devices.  Auxiliary field devices (i.e., 4-20 mA devices) that don’t 

use ½ wave rectification must be powered separately. 
 

Network & Cabling Requirements (Only RTS-20Jxx) 

 

To ensure network stability and reliable communications when using the Service Port 

option, particularly at high speeds on a BACnet RS-485 MS/TP network, it is imperative 

that you adhere to the following network and cabling requirements: 

 

Item 

Description 

Cabling 

For BACnet MS/TP networks it is recommended that you use network cabling 

that matches the following specifications: 

 

Balanced 100 to 120 ohm nominal impedance Twisted Shielded Pair 

(TSP) Cable 

 

Nominal capacitance of 16 PF/FT or lower  

 

Nominal velocity of propagation of 66% or higher 

Topology 

For BACnet MS/TP networks, ensure the cable is installed as a 

daisy-chain

 

from one device to the next. 

Max. Nodes  The maximum number of devices per BACnet MS/TP network without any 

repeaters is 

50

Termination 

Boards 

A termination board 

must

 be installed at each end of each BACnet MS/TP 

network segment – or two per BACnet MS/TP network.  Ensure you do not 

overlook this in laying out your network architecture and ordering product. 

Repeater 

A repeater (RPT-768) is not necessary unless more than 50 nodes will be 

installed on a network 

or

 you need to extend the network beyond 4000 ft (1220 

m). 

Содержание RTS-20 Series

Страница 1: ...RJ 11 service port and an Occupancy Override Push button and Setpoint Adjustment Thumb Wheel Room Temperature Sensors are ideal for providing remote temperature sensing occupancy override for room sch...

Страница 2: ...rride Pushbutton 9 9 9 20k Setpoint Adjust Dial 9 9 9 Accessories for the RTS 20Jxx TRM 768 Delta Network Terminator for MS TP RPT 768 Delta Network Repeater for MS TP Package Contents Room Temperatur...

Страница 3: ...ional RJ 11 Service Port jack 6 wire Wiring 2 for optional BACnet MS TP service port connection 100 120 ohm balanced TSP cable 16 PF FT or lower 2 for optional service port power 2 for temperature 1 e...

Страница 4: ...ing section for more details The second is a 20k potentiometer for Setpoint adjustment that must also be programmed and set by Jumper as required See Setpoint Scaling for details Setpoint Scaling for...

Страница 5: ...al end of scale reading Note Do NOT connect the Override output to the controller unless you have the jumper in the OVERRIDE position Doing so may skew the actual resistance read in the Thermistor or...

Страница 6: ...connections for each input connect the Common from the RTS 20JPS to each Input ground terminal The labeling on the backplate of the RTS 20JPS is labeled TMP for the 10k Thermistor SET for the 20k Setp...

Страница 7: ...optional 24VAC with RTS 20J and RTS20JPS Optional Push button with RTS 20JP Thermistor Connector Posts for optional Temperature Sensor Connector Posts for optional Push Button Override Connector Post...

Страница 8: ...r RTS 20xxx Rev 3 0 Installation Application Guide Page 8 of 13 Document Edition 2 3 RTS 20P RTS 20S and RTS 20PS Assembled on to the BACstat II top plate RTS 20 Assembled on to the BACstat II bottom...

Страница 9: ...ely Network Cabling Requirements Only RTS 20Jxx To ensure network stability and reliable communications when using the Service Port option particularly at high speeds on a BACnet RS 485 MS TP network...

Страница 10: ...Room Temperature Sensor RTS 20xxx Rev 3 0 Installation Application Guide Page 10 of 13 Document Edition 2 3 For more detailed information including wiring refer to the Delta Controls Wiring Guidelines...

Страница 11: ...o I O BACstat II with muxed I O I O Field Modules LINKnet Devices TRM Level 4 Network LINKnet DFM DFM TRM LINKnet Notes 1 Ensure you use the recommended balanced cable 2 Ensure the cable is installed...

Страница 12: ...ton The following program is an example of how to read the temperature of the Room Temperature Sensor without the pushbutton interfering Objects created in the same panel that the RTS is connected to...

Страница 13: ...y be required to de energize the equipment before servicing All terminals are acceptable for Class 2 circuit connection only CAUTION Input Class 2 Power Supplies are interconnected To Reduce the Risk...

Отзывы: