Setup

To set up the O3 Edge using the Proviso app, you must have Bluetooth

®

 and location services enabled on your 

mobile device . For best performance, your device should support Bluetooth Low Energy (BLE) version 5.0 or 

later.

Connecting to the O3

1.  Open the Proviso app and select 

Bluetooth 

for your connectivity method

.

Note

Select NFC only when you want to factory reset your device. To reset your device, select   in the upper right corner of the screen, 

then select 

Reboot hub

. A confirmation appears. To continue, select 

Yes, reboot hub

.

2.  Select an O3 to initiate a connection. Nearby O3 devices are listed by their Bluetooth MAC address.  

The selected O3 plays a sound and the light ring flashes blue.

3.  If this is the correct device, select 

Yes, connect

. Data loads from the O3 and the status changes to 

Connected

. You can now view device information and sensor data from the O3 in the 

Diagnostics

 tab. This 

data is transferred securely over Bluetooth from the O3 to your mobile device.

Configuring the O3

1.  After connecting to the O3, go to 

Settings

 > 

Network

. If you want to assign a static IP address, select  , 

select 

Static

, enter the IP settings, then select 

Save

. Otherwise, leave it as 

DHCP

. The IP address must be 

unique for each O3.

2.  Configure a network connection: IP, Ethernet, or Secure Connect. 

Note

:

 You cannot enable Ethernet or IP at the same time, but you can enable Secure Connect as a second port. The O3 will not route 

between interfaces. That is, you cannot route Secure Connect to Ethernet, Secure Connect to IP, etc.

•  To connect BACnet UDP/IP, next to BACnet UDP/IP, select  . Select enable

 Network, 

then enter the 

default UDP port number

 

to activate the IP protocol. Select 

Save

.

•  To connect BACnet Ethernet, next to BACnet ethernet, select  . Select enable 

Network

 to activate the 

Ethernet protocol. Select 

Save

.

•  To connect BACnet Secure Connect, next to BACnet SC, select  . Select enable 

Network

, then enter the 

Auto config URL from your enteliWEB site. Select 

Save

3.  Next to Security, select  , enter a 6-digit PIN to secure BLE read/write access to the hub, then select 

Save

. If you have migrated from the O3 Setup app, you must use the same PIN to access the hub in Proviso.

4.  Select 

Apply settings to hub

. After the settings are applied, the status shows 

Configured

 and a green 

check mark appears next to each applied setting.

Calibrating the O3

1.  After connecting to the O3, go to 

Settings

 > 

Calibration

 and select  .

2.  Measure the temperature below the O3 at occupant height, enter the temperature in the 

Actual 

temperature

 field, then select 

Save

3.  If you plan to use the O3 for lighting control, adjust the lighting in the space to the desired brightness, 

record the current reading in the 

Hub reading at desired light level

 field, then select 

Save

. This setpoint 

will be used by the control system as a baseline for control loops. 

4.  Select 

Apply settings to hub

.

Upgrading the firmware (requires internet connection)

1.  After connecting and applying settings to the O3, in the Proviso app, select   in the upper right corner of 

the screen, then select 

Upgrade firmware

.

2.  Under 

Firmware upgrade method

, select 

Select version from list

.

3.  Select the firmware version you want to upgrade to, then select 

Apply firmware upgrade

.

4.  Click 

OK

 to continue. The light ring is orange while the upgrade is in progress.

Note

:  Do not power off or reboot the O3 while the light ring is orange. If the light ring flashes red three times, there was an error during 

the upgrade process. Check your network connections and settings.