Menu Item
Description
The LCD Display Code Setting (AV15), a 4-digit value (ABCD) configures local
display and button handling as follows:
A
Line 1 (Top Left – i.e., Outside Value): 1 to 4
1
- Disabled
2
- Value from AV5 (i.e., remote value such as OAT)
3
- Value from AI2 (i.e., external sensor)
4
- Value from AI3 (i.e., Humidity)
B
Line 2 (Center – i.e., Inside Value): 1 to 4
1
- Disabled
2
- Temperature from AI1
3
- Humidity from AI3
4
- Alternates between Temperature (AI1) & Humidity (AI3)
5
- Value from AI2 (i.e., external sensor)
6
- Value from AV5 (i.e., remote value
7
- Setpoint
8
- Setpoint with adjust
9
- User Setpoint with adjust (-3 to +3 degrees)
C
Line 3 (Bottom – i.e., Setpoint Value): 1 to 5
1
- Disabled
2
- No Setpoint until an arrow button is pressed (adjustable)
3
- Setpoint is always displayed (adjustable)
4
- No Setpoint until an arrow button is pressed (not adjustable)
5
- Setpoint is always displayed (not adjustable)
6
- Temperature from AI1
7
- Value from AI2
8
- Humidity from AI3
9
– CO2 from AI4
D
House & Day/Night Mode Icons: 1 to 9
H
OUSE
O
UTLINE
O
N
/O
FF
T
EXT
M
AN
S
UN
/M
OON
1
No
No
No
No
2
No
Flash
No
No
3
No
Yes
No
No
4
No
No
No
Yes
5
Yes
No
No
No
6
Yes
Yes
No
No
7
Yes
Yes
Yes
No
8
Yes
No
Yes
No
9
Yes
No
No
Yes
N
OTE
: When connected to MS/TP, the Display Code may be set to any valid value –
making it unnecessary to write GCL+ programs for display and button handling.
Whenever an application is selected, a matching default Display Code is also set
automatically (typically 1237), but this can be set to something else if so desired.