DeLonghi Bran 0011M H Скачать руководство пользователя страница 16

16

BRAN H  

GB 03/2009

OPERATING CHARACTERISTICS

I A

Temperature control

Control is performed based on the system water return tem-
perature.
The set points refer to the water return temperature. 
The water outlet temperature depends on the difference
between inlet and outlet, usually 5°C (rated). 
This temperature difference may change depending on the
type of water circuit. 
For example, if the HEAT set point is set to +30°C, the outlet
temperature will be +35°C.
The return temperature is also used to activate the
resources inside or outside unit (e.g. electric heaters).
The controller features Full Floating technology that optimis-
es, when the scan time elapses, the water temperature set
points (HEAT/DHW) in relation to the compressor operating
time and the water temperature. 
To display the actual set point, select directory Sr and the
active operating mode (Heat, DHW), as described in the
paragraph "Displaying installer parameters".

Heating set point

(factory setting) = 40°C, Hysteresis = 3°C.
The compressor starts at outlet water temperatures below
37°C.
The compressor stops at water temperatures above 40°C.

In the event of temporary power failure, when power returns,
the mode set previously will be retained in the memory.

COMPRESSOR START UP DELAY

Two functions prevent the compressor from starting up too
frequently:
- Minimum time since last shut-down 3 minutes.
- Minimum time since last start-up 5 minutes.

CIRCULATING PUMP

The electronic board has an output for managing the circu-
lating pump, always on in HEAT modes, and off with a 1
minute delay when unit shuts down (standby). 
After the first minute of pump operation when the water flow
is at full speed, the water flow alarm functions are activated
(differential pressure switch and flow switch).

FAN SPEED CONTROL

To enable the unit to function correctly at different outside
temperatures, a microprocessor with pressure reading via
temperature sensor controls the fan rotation speed. This
allows the exchange of heat to be increased and/or
decreased, maintaining condensing or evaporation pres-
sures essentially constant. The fan operates independently
of the compressor.

FROST ALARM

The frost protection function is always active even if the con-
troller is standby.
To prevent the water freezing and damaging the plate heat
exchanger, the microprocessor shuts down the compressor
if the temperature measured by the heat exchanger outlet
temperature sensor is less than +4°C. 
The frost prevention temperature set point can be modified
by an authorised service centre only and only after verifying
that the water circuit contains antifreeze.
Tripping of this alarm shuts down the compressor but not
the pump, which remains active.

To reset normal functions, the water outlet temperature must
rise to more than +7°C. Reset is automatic.
If the frost alarm is tripped more than 3 times in one hour,
reset becomes manual.

DOMESTIC HOT WATER FROST PROTECTION 

The domestic hot water frost protection function is only
active if an auxiliary resource is installed for the domestic
hot water storage (parameter CL61=28).
The auxiliary resource is activated if the water temperature,
measured by sensor BT4, is less than +5°C, and is deacti-
vated at +7°C.

WATER FLOW ALARM

The microprocessor manages a water flow alarm controlled
by a differential pressure switch installed as standard on the
unit, and a flow switch to be installed on the water outlet pip-
ing.
This safety device may trip after the first 60 seconds of
pump operation, if the water flow-rate is not sufficient.
The alarm shuts down the compressor and not the pump,
which remains active if the alarm lasts less than 20 sec-
onds, otherwise the unit is shut down completely.

DYNAMIC DEFROST

The unit manages the defrosts by reversing the refrigerating
cycle, switching the position of the reversing valve and oper-
ating the circuit in cooling mode for a few minutes with the
fans off.
The defrost cycle removes the ice that forms on the surface
of the outdoor heat exchanger external at low temperature
and high humidity.
The unit controller features smart defrost management in
relation to the temperature read by the outside air tempera-
ture sensor and the pressure in the refrigerant circuit.
The graph of the function is shown below.
The defrost cycle is started if the evaporation pressure falls
below the effective start defrost set point, a value that may
change, as represented in the graph, in relation to the out-
side air temperature. 
A countdown starts, and only at the end is the cycle
reversed to cooling mode, if the pressure remains below the
effective start defrost set point
If the rises back above the effective start defrost set point,
the defrost timer is set to zero.
The defrost ends when the set pressure value is reached or
alternatively after a maximum time.

°C

0

-15

2,8

4,8

Outside air temperature

Refrigerant circuit pressure

bar

Содержание Bran 0011M H

Страница 1: ...INSTALLATION OPERATING SERVICE MANUAL Air water heat pumps heating only with domestic hot water production axial flow fans and water pump assembly GB BRAN 0011M H BRAN 0025M H BRAN 0041M H...

Страница 2: ...e product 4 Description of standard unit 5 Dimensioned drawings 6 Installation 6 Water connections 7 Water circuit data 9 Operating diagrams 10 Electrical connections 12 Mains power supply connections...

Страница 3: ...ces without authori sation and instructions from the manufacturer Do not pull detach or twist the electrical cables coming from the unit even when disconnected from the mains electricity supply Do not...

Страница 4: ...able handling equipment The instruction manual is an integral part of the unit and should therefore be read and kept carefully The packaging should not be removed until the unit is located in the inst...

Страница 5: ...nd on site installation is limited to water and electrical connections VERSIONS AVAILABLE BRAN H Air water heat pump heating only with domestic hot water production Built in water pump assembly comple...

Страница 6: ...ckaging To move the unit horizontally make appropriate use of a lift truck or similar bearing in mind the weight distribution of the unit To lift the unit insert tubes long enough to allow positioning...

Страница 7: ...n vessel Failure to install the flow switches will mean the heat exchangers are not protected in the event of no flow of liq uid Manufacturer cannot be held liable for any damage to the unit and or th...

Страница 8: ...ss than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm FILLING THE SYSTEM Before starting to fill place the unit mains switch QF1 in the OFF p...

Страница 9: ...ean evaporator plates fouling factor 1 For different fouling factors multiply the figures in the perfor mance tables by the coefficient given in the following table 4 4 x 10 5 0 86 x 10 4 1 72 x10 4 0...

Страница 10: ...r by managing a special 3 way valve connected to a hot water storage cylinder 1 Heat pump 2 Non return valve 3 Control valve with dial 4 Shut off valve 5 Expansion vessel if necessary 6 Air separator...

Страница 11: ...ng a special 3 way valve connected to a hot water storage cylinder 1 Heat pump 2 Non return valve 3 Control valve with dial 4 Shut off valve 5 Expansion vessel if necessary 6 Air separator 7 DHW stora...

Страница 12: ...be within a tolerance of 10 of the rated power supply voltage for the unit for three phase units the unbalance between the phases must not exceed 3 If these parameters are not respected contact the e...

Страница 13: ...the inspection panel Check that all the covers removed to make the electrical connections have been replaced before powering up the unit Place the main switch QF1 outside the unit in the ON position T...

Страница 14: ...ving removed the jumper COMPRESSOR ON SIGNAL GN1 For remote display of the compressor operating status an audible or visual alarm warning device can be connected between terminals 10 and 11 Connect th...

Страница 15: ...8 38 38 37 37 37 37 45 45 45 45 44 44 44 44 43 43 43 43 42 42 42 42 48 49 50 51 47 46 KA8 0 KA7 52 53 12 13 KA7 11 10 10 RD1 2 1 11 12 KA9 23 23 0 4 M 1 E2 5 6 FU1 M C EV2 C3 blue black brown 1 2 3 4...

Страница 16: ...essor if the temperature measured by the heat exchanger outlet temperature sensor is less than 4 C The frost prevention temperature set point can be modified by an authorised service centre only and o...

Страница 17: ...er temperature sensor BT1 has reached the DHW set point AS01 plus a differential AS05 that considers the possible temperature difference between the domestic water storage and the system return water...

Страница 18: ...water management disabled 1 Domestic hot water production with heat pump only AS00 2 Domestic hot water production with additional DHW storage heater only e g electric heater 3 Domestic hot water prod...

Страница 19: ...ompensation in HEATING mode based on the outside temperature Graph with factory settings Outside air temperature Ds06 Ds02 10 C Ds06 5 C 28 C 33 C Water temperature set point Ds02 15 C Ds04 5 C Parame...

Страница 20: ...7 6 min 00 tE18 0 hours 7 tE45 6 min 00 tE46 0 tE73 tE74 Operating mode ON Standby ON tE19 0 ON tE47 0 tE75 TIME BAND 2 Cool set point tE20 12 tE48 12 tE76 Heat set point tE21 33 tE49 33 tE77 DHW set...

Страница 21: ...75 Heating capacity 1 kW 6 5 8 7 13 8 Power absorbed 2 kW 1 65 2 15 3 40 COP 2 3 94 4 05 4 06 Rated water flow 1 m3 h 1 12 1 50 2 37 Residual head 1 kPa 41 48 89 Fans n 1 1 2 Air Flow m3 s 0 9 1 1 9 T...

Страница 22: ...OPERATING LIMITS 15 10 3 7 20 25 25 35 40 50 55 45 7 t t HEATING OUTLET WATER TEMPERATURE C EXTERNAL AIR TEMPERATURE C Min max water thermal gradient 4 6 Min max water circuit pressure bar 1 3 Max sto...

Страница 23: ...emote keypad A4 see wiring diagram shows OFF if featured Close the door of the electrical panel Move the main unit switch QS1 to the ON position Move the switch QF1 outside the unit to ON The message...

Страница 24: ...previous level See section on Changing new settings operating mode Set Confirm Confirms value exit and save Main display Main Display Menu save new settings new settings See Main Display section Move...

Страница 25: ...rost 1 STATUS AND OPERATING MODE LEDS Compressor Not used Not used Fan System pump Domestic hot water function activation External auxiliary heating element activation 3 UTILITY LEDS Clock RTC Degrees...

Страница 26: ...r managing time bands to control specific events Follow the procedure shown below to set the hours minutes and date To enter menu CL press the set button Once having entered this menu HOUr will be sho...

Страница 27: ...27 GB 03 2009 BRAN H press the set button To exit the clock setting menu press the esc button until returning to the main display...

Страница 28: ...stand by HEAt heat Use the up and down buttons to select the desired operating mode SELECTING THE OPERATING MODE There are three different modes Standby mode StbY in standby the compressor and pump a...

Страница 29: ...the SP directory To enter the SP directory press the set button SETTING THE SET POINTS As an example the Set Point in HEAT mode will be changed from 45 degrees centigrade to 48 degrees centigrade di T...

Страница 30: ...To increase or decrease the value use the up and down buttons For example to change the set point to 48 degrees press the up button until the desired value is displayed To return to the main display...

Страница 31: ...nputs config ured as digital inputs the value will be 0 input inactive for digital inputs this corresponds to the input being open for analogue inputs configured as digital inputs it corresponds to th...

Страница 32: ...nter the password installer or manufacturer press set and exit Access the parameters to display or change the values Press the up and down buttons to select the Par submenu Press the set button to dis...

Страница 33: ...sing the up and down buttons until reaching label Hr DISPLAYING AND RESETTING COMPRESSOR PUMP HOURS Press the set button to display the first label in this case the operating hours for compressor 1 CP...

Страница 34: ...ANUAL RESET To reset the alarm manually press the UP and DOWN but tons at the same time UP DOWN NOTE resetting an alarm that is still active saves the event in the alarm log MUTING AND MANUALLY RESETT...

Страница 35: ...he first alarm is Er01 Scroll any other active alarms using the UP and DOWN buttons NOTE the menu is not cyclical For example if alarms Er01 Er02 and Er03 are active the display will be Er01 Er02 Er03...

Страница 36: ...the directory FnC Press the set button to access the Functions menu The first label displayed is dEF Use the UP and DOWN buttons to select directory EUr Press the set button for 3 seconds The display...

Страница 37: ...Forced capacity control tE PAR tE tE00 AL92 Time bands AL ALarm AL00 AL82 Alarms Note when setting the parameters the COMPRESSOR and HEATER LEDs will flash alternating with the DEFROST LED FAULT CAUS...

Страница 38: ...eset Check electrical connections Replace component Values display indication Er60 Faulty BT1 water return sensor automatic reset Check electrical connections Replace component SHUTTING DOWN FOR LONG...

Страница 39: ...A refrigerant must only be charged in the liq uid state Operating conditions other than rated conditions may produce considerably different values Tightness testing or identification of leaks must onl...

Страница 40: ...nt Check Check Check Protection devices trip and shut down the com pressor Excessive discharge pressure Low suction pressure Low voltage Electrical connections not sufficiently tight Operation outside...

Страница 41: ...mpty and refill Faulty operation of outside heat exchanger control pressure regulating valves Check High suction pressure greater than 10 bars High utility water inlet temperature Thermostatic expansi...

Страница 42: ...Climaveneta Home System Via Duca d Aosta 121 31030 Mignagola TV Italia Tel 39 0422 4131 Fax 39 0422 413659 COD 5790003200_01...

Отзывы: