Installation and Setup
Installing a PS4000 Array
2–5
Environmental Requirements
You must meet these environmental requirements for a PS4000 array:
•
Only operate an enclosure from a power source with a voltage range of 100 to
240 VAC.
•
Make sure each power source has sufficient electrical overload protection.
•
Make sure there is sufficient space for air flow in front of and behind the
array.
•
Make sure the location is properly vented.
•
Review the technical specifications in Table 2-2 to make sure your
environment supports its requirements.
Table 2-2: PS4000
Technical Specifications
Component
Requirement
Weight of fully-loaded array
77.6 pounds or 35 kilograms
Operating temperature
41 to 95 degrees F / 5 to 35 degrees C
Storage temperature
-22 to 140 degrees F / -30 to 60 degrees C
Operating altitude
10,000 feet (3048 meters)
Operational relative humidity
20 to 80 percent non-condensing
Thermal output (fully-loaded array) 1700 BTU/hour (SAS disks)
1550 BTU/hour (SATA disks)
Operational shock
5 G for 10 ms 1/2 sin
Operational vibration
Random 0.21grms 5 - 500 Hz
Input voltage
100 to 240 VAC (auto-sensing)
Input frequency
48 - 62 Hz
System input power
530 VA (maximum)
Each power supply
450 watts DC output
Maximum input power: 0.7 KVA
Input current: 7 – 3.5A
Dimensions
5.12 in. x 19 in. x 21.7 in.
(13 cm x 48.26 cm x 55.1 cm)
Содержание PS Series