Table 36. Maximum shock specifications
Maximum shock
Specifications
Operating
Six consecutively executed shock pulses in the positive and negative x,
y, and z axes of 6 G for up to 11 ms.
Storage
Six consecutively executed shock pulses in the positive and negative x,
y, and z axes (one pulse on each side of the system) of 71 G for up to
2 ms.
Table 37. Maximum altitude specifications
Maximum altitude
Specifications
Operating
3048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Table 38. Operating temperature de-rating specifications
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above
950 m (3,117 ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above
950 m (3,117 ft).
40°C to 45°C (104°F to 113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above
950 m (3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous
contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Table 39. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE:
The ISO Class 8 condition applies to data center
environments only. This air filtration requirement does not apply
to IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data center
environments.
Corrosive dust
●
Air must be free of corrosive dust.
●
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE:
This condition applies to data center and non-data center
environments.
Table 40. Gaseous contamination specifications