Thermal specifications for the PowerEdge M610x are detailed in Table 3 along with other important
operating and storage information.
Table 3.
Operating and Storage Specifications
Temperature
Operating
10
o
to 35
o
C (50
o
to 95
o
F) with a maximum temperature gradation of
10
o
C per hour
Note: For altitudes above 2950 feet, the maximum operating
temperature is derated 1
o
F/500ft
Storage
-40
o
to 65
o
C (-40
o
to 149
o
F) with a maximum temperature gradation
of 20
o
C per hour
Relative Humidity
Operating
20% to 80% (noncondensing) with a maximum humidity gradation of
10% per hour
Storage
5% to 95% (noncondensing) with a maximum humidity gradation of
10% per hour
Maximum Vibration
Operating
0.26 Grms at 5-350 Hz in operational orientations
Storage
1.54 Grms at 10-250 Hz in all orientations
Maximum Shock
Operating
Half sine shock in all operational orientations of 31 G +/- 5% with a
pulse duration of 2.6 ms +/- 10%
Storage
Half sine shock on all six sides of 71 G +/- 5% with a pulse duration
of 2 ms +/- 10%
Altitude
Operating
-15.2m to 3048 m (-50 to 10,000 ft)
Note:
For altitudes above 2950 ft, the maximum temperature is
derated 1
o
F/550 ft
Storage
-16 to 10,600 m (-50 to 35,000 ft)
Airborne contaminant level
Class G1 or lower as defined by ISA-S71.04-1985 (G1 maximum corrosive contaminant levels
measured at ≤ 50% relative humidity)
5.4
Acoustics
The acoustical design of the PowerEdge M610x reflects adherence to Dell’s high sound quality
standards. Sound quality is different from sound power level and sound pressure level in that it
describes how humans respond to annoyances in sound, like whistles or hums. Definitions for
acoustical performance data are as follows:
•
Idle:
Reference ISO7779 (1999) definition 3.1.7; system is running in its OS but no other
specific activity.
•
LwA–UL:
The upper limit sound power level (LwA) calculated per section 4.4.2 of ISO 9296
(1988) and measured in accordance to ISO 7779 (1999).