Table 24. Environmental specifications (continued)
Type
Condition
Temperature or Specification
Operating
0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage
1.88 G
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides
tested).
Maximum Shock
Operating
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes of 40 G for up to 2.3 ms.
Storage
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Maximum Altitude
Operating
3,0482000 m (10,0006560 ft)
Storage
12,000 m (39,370 ft)
Operating Altitude De-rating
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1 °C/300 m (1
°F/547 ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1 °C/175 m (1
°F/319 ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1 °C/125 m (1
°F/228 ft) above 950 m (3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility
of the customer.
NOTE:
This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified in the
following table and are the reason for the damage and/or failures to your equipment, it may be necessary for you to
re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental
conditions will be the responsibility of the customer.
Table 25. Particulate contamination specifications
Particulate contamination
Specifications
Air Filtration
NOTE:
Applies to data center environments only. Air filtration
requirements do not apply to IT equipment designed to be used
outside a data center, in environments such as an office or
factory floor.
Data center air filtration as defined by ISO Class 8 per
ISO 14644-1 with a 95% upper confidence limit.
NOTE:
Air entering the data center must have
MERV11 or MERV13 filtration.
Conductive Dust
NOTE:
Applies to data center and non-data center
environments.
Air must be free of conductive dust, zinc whiskers, or
other conductive particles.
Corrosive Dust
NOTE:
Applies to data center and non-data center
environments.
●
Air must be free of corrosive dust.
●
Residual dust present in the air must have a
deliquescent point less than 60% relative humidity.