21
Installation and Startup
|
Installing the Input and Ground Wires
1
2
3
4
Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach
a flexible metal fitting to the end of the conduit.
5
Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
Strip 0.5
”
(1.5 cm) of insulation from the end of each incoming wire.
6
Connect the input and ground wires to the terminal block according to the UPS Wiring
Specifications in the following table.
Wire Function
Terminal
Position
UPS Wire Function
Terminal Wire
Size Rating*
Tightening Torque
Input
1
Input Ground
16–35 mm
2
(8–2 AWG)
1.7 Nm (15 lb-in)
2
L2/Neutral In
3
L1 In
* Use a minimum:
S
8 AWG for equipment grounding wire, 75
_
C copper wire minimum
S
4 AWG for input line and neutral wires, 75
_
C copper wire minimum
7
Replace the terminal block cover.