Installation and Configuration

WARNING:

 Before performing the following procedure, review the safety instructions that came with all Storage Center

components.

Topics:

Unpacking the System

Installation Safety Precautions

Installation Overview

Connecting the Power Cables

Securing the Power Cables

Location of Power Switches

Unpacking the System

NOTE:

 Unpacking, installing, and deploying your Storage Center may be done only by a certified service technician.

Before you begin, make sure the site where you intend to set up and use the Storage Center has the following:

208 V power from an independent source or a rack power distribution unit with a UPS. (110 V power will not work.)

Storage Center with the latest firmware, BIOS, and drivers. Contact your supplier for the correct software versions.

A 5U space in the lower 20U of the rack. If planning to install above the 20U mark, a customer-provided mechanical lift must be made
available.

Installation Safety Precautions

Follow these safety precautions to avoid injury and damage to Storage Center equipment:

Dell recommends that only individuals with rack-mounting experience install a storage system in a rack.

You need at least two people to lift the storage system chassis from the shipping box and three people to install it in the rack. The
empty chassis weighs approximately 46 kg (101 lbs).

Make sure the storage system is fully grounded at all times to prevent damage from electrostatic discharge.

When handling the storage system hardware, you should use an electrostatic wrist guard (not included) or a similar form of protection.

The storage system chassis must be mounted in a rack; the following safety requirements must be considered when doing so:

The rack construction must be capable of supporting the total weight of the installed chassis and the design should incorporate
stabilizing features suitable to prevent the rack tipping or being pushed over during installation or in normal use.

When loading a rack, fill from the bottom up; empty from the top down.

To avoid danger of the rack toppling over, do not slide more than one chassis out of the rack at a time.

The system must be operated with low pressure rear exhaust installation.

The rack design should take into consideration the maximum operating ambient temperature for the unit, which is 35°C.

Installation Overview

The installation process follows the general steps below. For detailed information, refer to vendor documentation supplied with the
equipment.

CAUTION:

 If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack

environment may be greater than room ambient temperature. Therefore, consideration should be given to installing the
equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.
For more information, see 

Technical Specifications

.

1. Assemble the rails following the safety instructions and the rack installation instructions provided with your system.

2

Installation and Configuration

5

Содержание Compellent SC280

Страница 1: ...Dell Storage Center SC280 Enclosure Getting Started Guide Regulatory Model SP 2584 E11J ...

Страница 2: ...the problem WARNING A WARNING indicates a potential for property damage personal injury or death Copyright 2015 Dell Inc All rights reserved This product is protected by U S and international copyright and intellectual property laws Dell and the Dell logo are trademarks of Dell Inc in the United States and or other jurisdictions All other marks and names mentioned herein may be trademarks of their...

Страница 3: ...System 5 Installation Safety Precautions 5 Installation Overview 5 Connecting the Power Cables 7 Securing the Power Cables 8 Location of Power Switches 8 3 Other Information You May Need 9 4 NOM Information Mexico Only 10 5 Technical Specifications 11 Contents Contents 3 ...

Страница 4: ...y the operating ambient temperature of the rack environment may be greater than room ambient temperature Therefore consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature Tma specified by the manufacturer Safety Warnings A fully configured SC280 expansion enclosure weighs up to 131 kg 288 lb An unpopulated expansion enclosure weig...

Страница 5: ...event damage from electrostatic discharge When handling the storage system hardware you should use an electrostatic wrist guard not included or a similar form of protection The storage system chassis must be mounted in a rack the following safety requirements must be considered when doing so The rack construction must be capable of supporting the total weight of the installed chassis and the desig...

Страница 6: ...dy to push the drawer toward the chassis until the locks disengage 5 Insert each disk drive in carrier DDIC into the enclosure one at a time Protect the drive from static discharge Handle DDICs by the edges of the frame CAUTION If the enclosure system operates for too long depending on altitude with drive drawers open the enclosure can overheat causing power failure and data loss Such use may inva...

Страница 7: ...the OFF position before connecting the power cables Figure 2 Connecting the power cables CAUTION Be careful when closing the rear rack door to ensure that power cords have adequate space as some racks might not be sufficiently deep Installation and Configuration 7 ...

Страница 8: ...e other end of the power cables into a grounded electrical outlet or a separate power source such as an uninterrupted power supply UPS or a power distribution unit PDU Location of Power Switches Figure 4 Power switches NOTE Do not power up the enclosure until all Storage Center components are racked and cabled 8 Installation and Configuration ...

Страница 9: ...nt or as a separate document The rack documentation included with your rack solution describes how to install your system into a rack The Storage Center Deployment Guide provides information about cabling hardware components configuring a new Storage Center using the System Manager Setup Wizard and managing a Storage Center in System Administrator 3 Other Information You May Need 9 ...

Страница 10: ...in compliance with the requirements of the official Mexican standards NOM Importer Dell Inc de México S A de C V Paseo de la Reforma 2620 11 Piso Col Lomas Atlas 11950 México D F Model number SP 2584 E11J Supply voltage 200 240 V CA Frequency 50 60 Hz Current consumption 16 A 4 10 NOM Information Mexico Only ...

Страница 11: ...f Independent Disks RAID Controller Dell Compellent SC8000 Management RAID management using Storage Center System Manager version 6 4 1 or later Back Plane Board Connectors 84 SAS hard drive connectors Two sets of SBB connectors Five cooling fan module connectors Two power supply connectors Back Panel Connectors per SBB SAS connectors Asymmetric SAS Cabling for connection to the controller and for...

Страница 12: ...hree SAS ports and two for the module status Cooling module One single color LED indicator for module status One single color LED indicator for battery fault status not currently used One single color LED indicator for fan fault status Power Supply Unit PSU One single color LED indicator for PSU fault status One single color LED indicator for AC power fault status One single color LED indicator fo...

Страница 13: ...40 to 158 F with a maximum temperature gradation of 20 C per hour Relative humidity Operating 20 to 80 noncondensing with a maximum humidity gradation of 10 per hour Storage 5 to 100 noncondensing Maximum vibration Operating 0 21 g at 5 500 Hz for 15 min Storage 1 04 g at 2 200 Hz for 15 min Maximum shock Operating Half sine shock 5 g 5 with a pulse duration of 10 ms 10 in operational orientations...

Отзывы: