Site preparations
VEP4600 is universal customer premise equipment (uCPE). To connect the service provider edge or enterprise branch to the cloud, use
VEP4600 to host multiple virtual network functions (VNFs), such as SD-WAN, routing, firewall, and deep-packet inspection.
For more information about VEP4600 specifications, see Chassis physical design section in this document.
NOTE:
Install the platform into a rack or cabinet before installing any optional components.
Topics:
•
•
•
•
•
•
•
Site selection
CAUTION:
The expansion cards are intended for professional installation only.
CAUTION:
Professional installation instructions: Products with WIFI and Bluetooth capabilities need to be installed by
qualified personnel with RF and regulatory related knowledge. The general user shall not attempt to install or change
any wireless settings.
Install your equipment in restricted access areas. A restricted access area is one where service personnel can only gain access using a
special tool, lock, key, or other means of security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your platform meets the following safety requirements:
•
Near an adequate power source. Connect the platform to the appropriate branch circuit protection according to your local electrical
codes.
•
Environmental—platform location—continuous temperature range is from 0°C to 45°C (32°F to 113°F).
•
Operating humidity is from 5 to 90 percent non-condensing, continuous.
•
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or direct sunlight.
•
Away from sources of severe electromagnetic noise.
•
Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and access.
•
Install the platform in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA 75.
For more information about platform storage and environmental temperatures, see
.
Cabinet placement
Install VEP4600 only in indoor cabinets designed for use in a controlled environment.
Do not install the platform in outside cabinets. For cabinet placement requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA) standard.
Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
2
Site preparations
5
Содержание VEP4600
Страница 1: ...VEP4600 Setup Guide ...
Страница 21: ...XXXXXX xxxxxx Dealer Code Certification pending Specifications 21 ...