F5 & F15 Series Service and Installation Manual
13
Cond.
Duct
Fresh
Air
Dis-
Charge
Air
Top
View
11.00"
28cm
22.00"
56cm
Louver
Cutout
22.00"
56cm
Louver
Cutout
12.00"
30cm
Minimum
Distance
Between
Louvers
22.00"
56cm
An “air duct” should be constructed from the air-intake louver to the condenser. This is
recommended to prevent recirculation of discharge air.
Discharge air louver may be located further from fresh air louver or on the opposite side of
counter.
F5 units are designed to be operated with two supplied louvered
panels for proper air flow. Failure to provide the proper air flow
will void the warranty. Louver cut-outs are 22" by 11" (55.9cm
by 27.9cm) typical. Cut-outs are to begin a maximum of
4.00" (10.2cm) from the counter-top. Proper installation must
provide for air flow to and from the condensing unit. Install as
shown below.
Condenser Air Flow: F5
Discharge Air
Fresh Air
Louver
Louver
Cond.
48" Wide Units Air Flow Detail
72" Wide Units Air Flow Detail