INSTALLATION & OPERATION MANUAL

SONAC/120 LIQUID LEVEL SWITCH

DECEMBER 2008 REV 1.0

1.0  INTRODUCTION

1.1 

Description

This  device  is  a  single  point,  electronic  switch  for  ON-

OFF level control of liquids, at temperatures from -65ºF                     

(-54ºC) to 400ºF (204ºC) and pressures to 4000 psi.

Typical applications include, crude and refined petroleum, 

hot asphalt, solvents, chemicals, liquefied air fractions, LPG, 

LNG, and most other liquids

1.2

 

Principle of Operation

The  SONAC/120  Switch  is  comprised  of  a  sensor, 

interconnecting cable and electronic control unit.

The  sensor  is  a  magnetostrictive  device  consisting  of  a 

diaphragm, nickel drive tube, bias magnet, drive coil and 

pickup coil.  The sensor diaphragm is electronically driven 

to oscillate at its resonant frequency with a high-velocity, low 

amplitude motion.  When the product level covers the sensor, 

the diaphragm is dampened.  This produces a change in the 

output signal level from the sensor’s pickup coil.  The control 

amplifier, which is in a regenerative feedback loop circuit 

with the sensor, processes the signal change, and actuates 

the output relay for the desired end function.

SELF-TESTING FEATURE:        A logic network is included 

in the feedback loop to “prove” the mechanical and electrical 

integrity of the sensing circuit.  If an open or short circuit 

occurs in the sensor connecting cable, or control amplifier, 

the relay immediately transfers to the alarm condition.
1.3

 

Specifications

Supply Voltage

 

Normal

 

Absolute Limits

 

 

115 VAC 

95-135 VAC

 

 

230 VAC 

190-270 VAC

 

                              or  12-24 VAC 

 

 

12-24 VDC

 

Frequency, AC Power 

50-60 Hz 

45 Hz Minimum

Time Delay 

Standard, 

50 ms to 

 

 

Adjustable  15 seconds

Failsafe 

Switch selectable, High

 

 

or Low Level

Environmental Rating 

NEMA 4X, IP55

Control Unit

Temperature Amplifier 

-40 to 75ºC

Sensor Temperature, 

Temperature  and  pressure 

Pressure Rating 

limits vary with sensor    

 

model. Consult  SONAC/120  

 

data sheet for specification  

 

information.

Sensor Mounting/ 

1” NPTM

Process Connection

 

Distance-Sensor to Control  150 ft (45.7M with PVC  

 

Unit, Maximum

 

Insulated Cable (BLUE) 

 

100ft (30.5M) with TFE  

 

Insulated (WHITE)

Indicators 

Two, light emitting diodes (LED).

 

 

RED - Illuminated when product is   

 

 

present at sensor 

 

 

YELLOW - Illuminated when relay is  

 

 

energized

Output   

Relay, DPDT 2 Form C Contracts

 

 

5 A at 120 VAC Non-Inductive

 

 

3 A at 240 VAC Non-Inductive

 

3 A at 24 VDC Non-Inductive

Shipping Weight  Control:   5 Pounds (2.5 Kilograms)
 

Sensor: 

1.6 Pounds (.68) Kilograms

 

2.2

 

Mechanical

AMPLIFIER HOUSING

.875

(22.2)

2.00

(51)

6.000

(152.4)

1.062

(27)

8.625

(219)

2.00

(51)

3.00

(76.2)

9.375

(238)

1/2” Condult knockout 

8.187

(208)

5.179

(131.5)

INSTALLATION DRAWING

NOTE: DIMENSIONS IN PARENTHESES DENOTE MILLIMETERS

2.0  INSTALLATION

2.1  Unpacking

Remove the system from the shipping carton and check the 

nameplate  model  number  against  the  packing  list  before 

destroying any packing material.  Remove plastic protective 

closures from sensor

Содержание SONAC 120

Страница 1: ...N OPERATION MANUAL SONAC 120 LIQUID LEVEL SWITCH DECEMBER 2008 REV 1 0 1 An L J Technologies Co 5911 Butterfield Road Hillside IL 60162 Phone 708 236 6000 Fax 708 236 6006 INSTALLATION OPERATION MANUA...

Страница 2: ...w level switches for the boiler process and liquid storage industries On February 28 2000 L J purchased Durlam Associates now Durlam Inc is located in Houston Texas and is the leading manufacturer of...

Страница 3: ...oduction 4 1 1 Description 4 1 2 Principle of Operation 4 1 3 Specifications 4 2 0 Installation 4 2 1 Unpacking 4 2 2 Mechanical Installation 4 2 3 Electrical Installation 7 3 0 Operation 7 3 1 Genera...

Страница 4: ...cable or control amplifier the relay immediately transfers to the alarm condition 1 3 Specifications Supply Voltage Normal Absolute Limits 115 VAC 95 135 VAC 230 VAC 190 270 VAC or 12 24 VAC 12 24 VD...

Страница 5: ...Tri Clamp Type 16 amp 34 1 5 38 1 pipe size FIGURE 1 1 11 1 2 NPT 25 4 Stainless Steel Sensor 625 15 9 1 3125 33 3 Cable Connector 5625 14 3 Single Sensor Sanitary Ladish Fitting USDA Approved for AA...

Страница 6: ...8m must have capacitor C1 removed see Figure 4 For TFE insulated cable WHITE the length must not exceed 100ft or 30 5M White cable length over 50ft or 15 2m must have capacitor C1 removed see figure...

Страница 7: ...ed 15 Not Used 16 Low Voltage Input 24 v AC or DC 17 Low Voltage Input 18 Not Used 19 Not Used 20 Sensor White or Clear Lead 3 0 OPERATION 3 1 General 3 2 1 Time Delay A20 turn potentiometer is furnis...

Страница 8: ...ay control CCW NOTE Time Delay Control Position Full Clockwise Greater than 10 seconds Full Counter Clockwise Less then 100 milliseconds 3 3 8 System is calibrated 4 0 MAINTENANCE SERVICE 4 1 One Year...

Страница 9: ...INSTALLATION OPERATION MANUAL SONAC 120 LIQUID LEVEL SWITCH DECEMBER 2008 REV 1 0 9 Page intentionally left blank...

Страница 10: ...OPERATION MANUAL SONAC 120 LIQUID LEVEL SWITCH DECEMBER 2008 REV 1 0 5911 Butterfield Rd Hillside IL 60162 PH 708 236 6000 FAX 708 236 6006 E MAIL sales ljtechnologies com REACHING NEW LEVELS IN PROC...

Отзывы: