DEKON D-BM100 OPTICAL BEAM 

SMOKE DETECTOR 

Doc:UM-D-BM100-0717-EN 

Page 4/16 

PURPOSE 

The D-BM100 Beam Smoke Detector is designed for smoke detection at the early stage of fire. It is particularly 
suitable for protection of premises where smoke appearance is expected in the first phase of the fire and 
where  installation  of  a  large  number  of  point  smoke  detectors  would  be  necessary  due  to  a  large  area. 
Compared to point smoke detectors, beam detectors are sensitive to a medium smoke density value on a 
long path of the infrared radiation beam. Therefore they are especially suitable for application under high 
ceilings/roofs or in those places, where smoke can be diffused over a large area before detection.  

Examples  of  applications,  where  this  type  of  detectors  can  be  particularly  useful,  include:  churches, 
cathedrals, monumental buildings with valuable historic ceilings, theatres, sports halls, industrial shops, very 
high rooms, in which point detectors would not be effective, and rooms with a differentiated ceiling or roof 
design.  
A distinctive feature of the D-BM100 detector is its arrangement of transmitter and receiver in one housing 
and  interaction  with  a  prism  reflector  or  a  reflector  panel  placed  on  the  opposite  wall.  A  single  casing 
embraces a laser pointer that enables optical path axis alignment between the detector and the reflector/set 
of reflectors.  

The D-BM100 beam smoke detector is intended to interoperate with any fire detection and alarm control 
panel that ensures power supply in the range between 9.5 V and 28 V and current > 100 mA. The alarm signal 
is  the  relay  non-potential  contact  switch  over.  The  detector  operates  in  closed  premises  at  ambient 
temperatures ranging from 

25

o

C to +55

o

C and relative humidity up to 95% at 40

o

C. 

TECHNICAL SPECIFICATIONS 

Operating voltage in a detection line 

 

9.5 

V ÷ 2

8.0 V 

Quiescent current from 9.5 to 28 V 

÷ 30 mA

 

Alarm current from 9.5 to 28 V   

20 ÷ 100 mA

 

PU and PA relay contact load    

max. 1 A/30 V 

Current at light beam interruption 

< 0.3 mA 

Current at service signal 

 optics contamination 

< 0.3 mA 

Sensitivity thresholds (to be chosen) 

 

18% (0,86 dB); 30% (1,55dB); 50% (3dB)* 

Operating distance  

-

 

with E39-R8 prismatic reflector (Fig. 6) 

from 5 m to 50 m  

-

 

with 4xE39-R8 set of reflectors (Fig. 7) 

from 50 m to 100 m 

Detector angular tolerance 

± 0.5°

 

Reflector angular tolerance 

± 5° 

 

Power supply of laser viewfinder (during alignment) 

6F22 (9 V) battery 

Operating temperature range   

-

25°C ÷ +55°C

 

Admissible ambient relative humidity   

up to 95% at + 40°C

 

Dimensions 

129 x 80 x 84 mm 

Mass (together with adjustment basis)   

0.35 kg  

Casing colour   

white (other on request) 

* 50% sensitivity threshold is not LPCB approved.

Содержание D-BM100

Страница 1: ...Doc No UM D BM100 0717 EN DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Installation and maintenance manual UM D BM100 0717 EN Revision 0...

Страница 2: ...Research Centre for Fire Protection CNBOP J zef w Poland an EU notified authority No 1438 confirming its compliance with the requirements of the PN EN 54 12 2005 standard Read the manual carefully bef...

Страница 3: ...ed Protection against ingress of foreign bodies 4 6 Passed Monitoring of detachable detectors and connections 4 7 Passed Additional requirements for software controlled detectors 4 9 Passed Electromag...

Страница 4: ...opposite wall A single casing embraces a laser pointer that enables optical path axis alignment between the detector and the reflector set of reflectors The D BM100 beam smoke detector is intended to...

Страница 5: ...ipped with automatic compensation mechanism to monitor its contamination and environment impact conditions The circuits guarantee the same sensitivity level in the whole compensation range At a certai...

Страница 6: ...100 m or with the D BM50 1 prism reflector operating distance is from 5 m to 50 m Set of reflectors single reflector test foil and an adjustment mirror are not included in the detector standard pack a...

Страница 7: ...sting operation especially in dusty premises may result in contamination dust dirt accumulation of the optical part of the detector and of the reflector set of reflectors After exceeding a determined...

Страница 8: ...and masks during detector installation works that produce high amount of dust such as hole drilling for detector base mounting on ceilings walls 7 4 Eye protection against laser beam operating equipm...

Страница 9: ...beam and a side wall of room should not exceed D value and between two adjacent detector beams 2D The distance from the IR beam to any obstacle e g a wall perpendicular to a side wall shall not be sho...

Страница 10: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 10 16 Fig 3 D BM100 design and overall dimensions...

Страница 11: ...TOR Doc UM D BM100 0717 EN Page 11 16 Fig 4 D BM100 detector installation wires connection Fig 5 D BM100 detector internal connections and output terminals diagram Power supply Connection of detection...

Страница 12: ...er in W1 position sustain of alarm condition after detector s activation the alarm relay changes its position and stay unchanged as long as the power supply is on Short brake of power supply of the de...

Страница 13: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 13 16 Fig 7 D BM100 detectors connection into detection line...

Страница 14: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 14 16 Fig 8 D BM50 1 prism reflector Fig 9 D BM100 4 set of reflectors...

Страница 15: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 15 16 Fig 10 D BM100 detector testing foil with overprints...

Страница 16: ...DEKON D BM100 OPTICAL BEAM SMOKE DETECTOR Doc UM D BM100 0717 EN Page 16 16 Fig 11 Assembly set of reflectors and the service mirror...

Отзывы: