background image

RECEIVING 

AND STORAGE

Receiving Inspection

Upon receipt, and at the time of actual unloading, 
each package should be visually inspected for any
possible damage or electrolyte leakage. If either is 
evident, a more detailed inspection of the entire 
shipment should be conducted and noted on the 
bill of lading. Record receipt date, inspection data 
and notify carrier of any damage.

Unpacking
(Always wear eye protection.)

1. Never lift batteries by the terminal posts. Always lift

batteries by the bottom or use the lifting handle.

2.  Check all batteries for visible defects such as 

cracked containers, loose terminal posts, or other 
unrepairable problems. Batteries with these defects
must be replaced.

Storage

1.  Cells should be stored indoors in a clean, level, dry

and cool location. Recommended storage tempera-
tures are 0°F to 90°F (–18°C to 32°C).

2.  Lead acid batteries self-discharge and must be given 

a boost charge periodically to prevent permanent 
performance degradation. Batteries should not be
stored for more than 180 days without applying a
boost charge of 13.8 volts ± .06 volts per battery
until the current stabilizes. 
Record dates and condi-
tions for all charges during storage.

INSTALLATIONS

Cabinets

Cabinet systems come factory assembled and
prewired. Do not tip or turn cabinets on their sides
when positioning them in their intended installation
area. Cabinets must be used in an upright position.
These systems are preconnected. Only inter-shelf,
inter-cabinet and connections to the load are 
required. See the connection diagram inside the 
cabinet. Inter-cabinet and load connection cables 
are not included.

Racks

Assemble racks in accordance with the intended 
arrangement, align with a level and bolt to the floor. 
See rack assembly instructions.

BATTERY 

ASSEMBLY

(Always wear eye protection.)

1. Set up the batteries so that the positive post (+) of one battery 

is connected to the negative post (–) of the next battery for 
all series connections. Make sure they match the connection
diagram. For parallel or parallel/series combinations, check
the connection diagram.

2.  The intercell connection contact surfaces should be cleaned

by rubbing gently with a non-metallic brush or pad before
installing connectors. 

3.  Install all intercell connections loosely to allow for final 

alignment of batteries, then torque to 60± 5 inch pounds.

General

1. Install the lockwasher and torque the terminal bolts or nuts 

to 60 ± 5 inch pounds. DO NOT OVERTORQUE. Some 
batteries have cable harnesses (torque value is 60 ± 5).

2. Clean all outside surfaces of batteries, cabinets and 

racks with soapy water only. DO NOT USE SOLVENTS.

3. For future identification of all racked batteries, apply 

individual battery numbers in sequence beginning with 
number one at the positive end of the first battery.

4.  After torquing the connections on racked batteries, read the 

voltage of the battery string to assure that individual batteries are
connected correctly. The total voltage should be approximately
equal to the number of batteries times the measured voltage of
one battery (when connected in series). If the measurement is
less, recheck the connections for proper voltage and polarity.

5.  Read and record intercell connection resistance and note 

the method of measurement. This helps determine a 
satisfactory initial installation and can be used as a reference
for future maintenance requirements. See Appendix A,
recording forms, in the back of the manual. Clean, remake
and remeasure any connection having a resistance 
measurement greater than 10% of the average of all the
same type of connections (intercell, inter-tier or shelf,
inter-rack or inter-cabinet).

6.  Battery performance is based on the output at the battery 

terminals. Therefore, the shortest electrical connections
between the battery system and the operating equipment r
result in maximum total system performance. 
Do not select cable size on current carrying capabilities
only 
Cable size should not provide a greater voltage drop
between the battery system and operating equipment than
specified. Excess voltage drop will reduce the desired 
support time of the battery system. Cables are not 
recommended for connecting parallel battery strings.

HIGH RATE SERIES

Содержание unigy

Страница 1: ...ated tools Procedures The following safety procedures should be followed during installation Always wear safety glasses or face shield 1 Adequately secure battery racks or cabinet enclosures to the floor 2 Connect support structures to ground system in accordance with applicable codes 3 Inspect all flooring and lifting equipment for functional adequacy Specifically review floor loading capacity 4 ...

Страница 2: ...r parallel or parallel series combinations check the connection diagram 2 The intercell connection contact surfaces should be cleaned by rubbing gently with a non metallic brush or pad before installing connectors 3 Install all intercell connections loosely to allow for final alignment of batteries then torque to 60 5 inch pounds General 1 Install the lockwasher and torque the terminal bolts or nu...

Страница 3: ...to be in excess of 95 F 35 C contact East Penn for recommendations Battery Battery High Rate Temperature Temperature Per Battery Float Voltage Degrees F Degrees C 06 volts 50 10 13 50 59 15 13 50 68 20 13 50 77 25 13 50 86 30 13 50 95 35 13 38 PERIODIC MAINTENANCE Always wear eye protection keep sparks and flames away Annual Inspection 1 Conduct a visual inspection of the battery ies 2 Record the ...

Страница 4: ...________________________________________________________ Date New ________________________ Battery location and or number __________________________________________________ Date Installed _____________________ Readings Taken By ____________________________ Remarks Recommendations __________________________________________________________ Readings should be taken at installation and annually therea...

Отзывы: