SYSTEM INSTALLATION
Cell Installation
Assemble system per the following details.
CAUTION: Never lift more than one cell at a time.
1. Ensure sufficient space has been allowed for proper and safe
battery installation and maintenance.
2. If cells are to be installed on a rack or cabinet, follow rack/
cabinet manufactures instructions for correct installation.
3. Batteries may be installed with posts in a vertical or horizontal
position. When installing in horizontal or vertical position,
ensure battery post are provided with ample clearance from
metal parts of rack/cabinet.
ELECTRICAL CONNECTION
Connector / Cable Assembly
1. The contact surfaces of each individual post on every cell has
been cleaned and coated with a thin film of NO-OX-ID “A” grease
at the factory. Ensure the contact surfaces are free of dust or dirt
prior to assembly. Re-application of NO-OX-ID “A” grease may
be required if post cleaning is required.
2. Connectors/cable lugs supplied with cells. It is recommended all
connectors/cables be coated with a thin film of NO-OX-ID “A”
grease.
3. Install the cables loosely to allow for final alignment. Spacing
between cells should be a minimum of 0.50” (12.7mm) for even
airflow around cells.
4. For multipost batteries (17 to 33 plate) a connector is to be
installed at the battery system positive and negative end of
each multiple cell configuration. This connector is used to
electrically tie all same polarity posts together.
5. Charging / load cable(s) should be tin or lead plated copper
lugs able to accept a 1/4 –20 bolt. Cable lugs should be coated
with a thin film of NO-OX-ID “A” grease. System connecting
cables can be attached to any battery post of the multipost
connector. System connecting cable(s) supplied by others.
Select cable size based on current carrying capability and
voltage drop.
6. Reference Appendix C for layout drawings detailing cable and
connector quantity and placement.
7. Upon completion of installing, all connectors / cables hardware
should be torqued to 125 ± 5 inch pounds (14.1 ± .5 Nm).