Installation and start up instructions RMC-142D
4189340158C (UK)
The design of the relay makes mounting of it close to other
uni-line
units possible,
however make sure there are min. 50 mm between the top and bottom of this relay and
other relays/units.
The DIN rail must always be placed horizontally when several relays are mounted on
the same rail.
4. Connection diagram
A 2A fuse may protect the auxiliary supply connection.
The relay is protected against ESD (electrostatic electricity), and further special
protection against this during the mounting of the relay is not necessary.
5. Start up instructions
5.1 Setting and indication
Setting of
LED/relay
Earth current set point
:
(10…110%) of I
n
Time delay:
(0-T1)
0…1/0…5/0…10 s
IE>> Yellow LED is lit when the set point has
been exceeded, but the output contact
has not yet been activated.
The contact is activated and the red
LED is lit after the timer has expired.
Earth current set point
:
(2…20%) of I
n
Time delay:
(0-T2)
0…20/0…60/0…120 s
IE>
Yellow LED is lit when the set point has
been exceeded, but the output contact
has not yet been activated.
The contact is activated and the red
LED is lit after the timer has expired.
At the factory the time delays are set according to the order specifications.