Level 2
Range
Over-speed Threshold
(OVER SPEED THRESH)
700 to 4000 RPM
Over-speed Delay
(OVER SPEED DELAY)
1 to 20 s
Gross Over-speed Threshold
(GROSS OS THRESHOLD)
100 to 200 %
Table 6.32
Battery Monitoring (BATTERY MONITOR)
Level 2
Range
Low Battery Voltage Action
(LOW VOLT ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
8.0 to 31.0 V
Low Battery Voltage Delay
(LOW VOLT DELAY)
5 to 1800 s
High Battery Voltage Action
(HIGH VOLT ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
High Battery Voltage Threshold
(HIGH VOLT THRESHOLD)
9.0 to 32.0 V
High Battery Voltage Delay
(HIGH VOLT DELAY)
5 to 1800 s
Table 6.33
Charging Alternator Monitoring (CHARGE ALT MON)
Level 2
Range
Charging Alternator Fail Action
(FAIL ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
Charging Alternator Fail Threshold
(FAIL THRESHOLD)
0.0 to 35.0 V
Charging Alternator Fail Delay
(FAIL DELAY)
5 to 60 s
Table 6.34
Preheating (PREHEAT)
Level 2
Range
Pre-heat Timer
(PREHEAT TIMER)
1 to 900 s
Engine Temperature
(ENG TEMP EN)
Enable
Disable
Engine Temperature Threshold
10 to 300 °C
USER MANUAL 4189341243A UK
Page 36 of 78