2.2.3 Parameter setup regulator governor
The table below illustrates the differences in the regulator parameter setup. In PPU-3, the possibility to adjust
the differential band in the regulator has been added.
Parameter setup regulator governor
Parameter
PPU-2
Description
Address
Parameter
PPU-3
Description
Address
2122
Freq. control
Kp
92
2511
f Kp
122
2123
Freq. control Ki
93
2512
f Ti
123
2513
f Td
124
2132
Power control
Kp
15
2531
P Kp
126
2133
Power control
Ki
50
2532
P Ti
127
2533
P Td
128
2.2.4 Parameter setup relay or analogue governor
In PPU-3, it is possible to change between relay and analogue governor setup, see the table below.
Parameter setup relay or analogue governor
Controller
Parameter
Description
Address
Set point
PPU-2
N/A
N/A
N/A
N/A
PPU-3
2781
Reg. output GOV
183
Relay or analogue
2.2.5 Parameter setup governor relay
The PPU-2 standard unit controls the governor on relay output terminals 65-68, slot #4, these are not configu-
rable. The PPU-3 standard unit has four configurable relay outputs, placed in slot #4, terminals 65-72. The
table below shows the differences in the standard parameter settings.
Parameter setup governor relay
Controller
Parameter
Description
Address
Value
Output A
Output B
PPU-2
2252
GOV period
time
122
ms
N/A
N/A
PPU-3
2602
GOV period
time
144
ms
Terminal 65
Terminal 67
ML-2 application notes Converting PPU-2
to PPU-3 4189341126 UK
Application and installation
DEIF A/S
Page 14 of 18