MULTI-LINE 2

APPLICATION NOTES

Converting PPU-2 to PPU-3

● Parameter conversion
● Wiring
● Options
● I/O list

Document no.: 4189341126A
SW version:

Содержание PPU-3

Страница 1: ...ww deif com isenborgvej 33 DK 7800 Skive Tel 45 9614 9614 Fax 45 9614 9615 info deif com www deif com 14 9614 Fax 45 9614 9615 info deif com www deif com MULTI LINE 2 APPLICATION NOTES Converting PPU 2 to PPU 3 Parameter conversion Wiring Options I O list Document no 4189341126A SW version ...

Страница 2: ...the application 5 2 1 1 General description 5 2 1 2 Converting the display 5 2 1 3 Description of options 6 2 2 Installation and parameter setup 11 2 2 1 Wiring installation 11 2 2 2 Parameter settings system setup 13 2 2 3 Parameter setup regulator governor 14 2 2 4 Parameter setup relay or analogue governor 14 2 2 5 Parameter setup governor relay 14 2 2 6 Synchronisation setup 15 2 2 7 Protectio...

Страница 3: ...war ranty will be lost Disclaimer DEIF A S reserves the right to change any of the contents of this document without prior notice The English version of this document always contains the most recent and up to date information about the product DEIF does not take responsibility for the accuracy of translations and translations might not be up dated at the same time as the English document If there ...

Страница 4: ...purpose of the application notes is to offer the designer information about suitable applications for the Multi line 2 unit Make sure to read this document before starting to work with the Multi line 2 unit and the gen set to be controlled Failure to do this could result in human injury or damage to the equip ment 1 2 2 Intended users The Application Notes are mainly intended for the person respon...

Страница 5: ...The table below shows an overview of standard displays and the options of converting the displays PPU 2 PPU 3 Note Protection and Paralleling Unit multi line PPU Self check Ready Regulator on JUMP INFO Alarm VIEW LOG REMOTE LOCAL BACK Open Closed Power Standard Protection and Paralleling Unit multi line PPU Self check Regulator on JUMP Alarm VIEW LOG MODE BACK Power JUMP START STOP G Remote Alarm ...

Страница 6: ... number of printed circuit boards PCBs mounted in numbered slots 1 3 4 and 5 Some of these board slots are standard and some are intended for options The board slot positions are arranged as illustrated below ML 2 application notes Converting PPU 2 to PPU 3 4189341126 UK Application and installation DEIF A S Page 6 of 18 ...

Страница 7: ...illustration below shows the location of the various options related to slots 2 4 6 7 and 8 ML 2 application notes Converting PPU 2 to PPU 3 4189341126 UK Application and installation DEIF A S Page 7 of 18 ...

Страница 8: ...ver under frequency generator and busbar Standard Software Option C1 Over under voltage generator Over under frequency generator Overload Fast over current 42 ms 350 2 levels Current voltage unbalance Reactive power import excitation loss Reactive power export over excitation Standard Software Option C2 Negative seq voltage current Zero seq voltage current Option C2 Software Power dependent reacti...

Страница 9: ...ngine communication CAN bus J1939 Option H7 Hardware N A CAN bus interface for external I O modules Beckhoff in slot 2 or slot 8 Option H8 x Hardware N A Modbus RTU ASCII RS 232 and GSM modem connection Option H9 2 Hardware Option J1 Display cable 3 m Standard Hardware Option J2 Display cable 6 m Option J2 Hardware Option J3 PC cable for utility software RS 232 N A Hardware N A PC cable for option...

Страница 10: ...ption Q1 Hardware N A Additional standard display on CAN bus Option X2 Hardware N A Additional Operator Panel AOP 1 Option X3 Hardware N A Additional Operator Panel AOP 2 Option X4 Hardware N A Front folio with engine and GB control Option Y1 Hardware N A Front folio with GB control Option Y5 GPU Hardware N A Front folio with engine control Option Y7 GPU Hardware Option Z1 PNOM 20 MW ML 2 applicat...

Страница 11: ...4 Digital input 24 Digital input Start sync control 25 Digital input 25 Digital input Common for terminals 23 27 28 Common 28 Common Modbus RTU RS 485 29 30 31 DATA DATA GND DATA 29 30 31 DATA DATA GND DATA Load sharing 37 38 39 Active load sharing Common Reactive load shar ing 37 38 39 Active load sharing Common Reactive load shar ing External f P set point 40 41 f P set point Common 40 41 f P se...

Страница 12: ...tween the ter minals Common for terminals 43 55 56 Common 56 Common Load dep start next DG 57 58 Relay 5 NO 57 58 Relay 57 NO Load dep stop next DG 59 60 Relay 6 NO 59 60 Relay 59 NO Analogue GOV output 20 mA 66 67 0 66 67 0 Analogue transducer out put 4 20 mA 70 71 0 70 71 0 I1 73 74 Current meas 73 74 Current meas I2 75 76 Current meas 75 76 Current meas I3 77 78 Current meas 77 78 Current meas ...

Страница 13: ...Nom fre quency 182 Hz 6001 Nom f 1 407 Hz 4012 Nom pow er 183 kW 6002 Nom P 1 408 kW 4013 Nom cur rent 184 A 6003 Nom I 1 409 A 4014 Nom volt age 185 V 6004 Nom U 1 410 V N A 6005 Nom RPM 1 411 RPM 4021 Volt prim GEN 186 V 6041 G primary U 428 V 4022 Volt sec GEN 187 V 6042 G secon dary U 429 V 4023 Current prim 188 A 6043 G primary I 430 A 4024 Current sec 189 A 6044 G secon dary I 431 A 4031 Vol...

Страница 14: ...setup see the table below Parameter setup relay or analogue governor Controller Parameter Description Address Set point PPU 2 N A N A N A N A PPU 3 2781 Reg output GOV 183 Relay or analogue 2 2 5 Parameter setup governor relay The PPU 2 standard unit controls the governor on relay output terminals 65 68 slot 4 these are not configu rable The PPU 3 standard unit has four configurable relay outputs ...

Страница 15: ...duMax 73 2023 Sync duMax 67 2024 Sync t CB 74 2024 Sync t GB 68 2041 Blackout dfMax 80 2111 Blackout dfMax 94 2042 Blackout duMax 81 2112 Blackout duMax 95 2043 Blackout ena ble 82 2113 Sync blackout enable 96 2 2 7 Protection setup The following adjustment points are available in PPU 2 Set points delay timer output A or B The protection has a commissioning window where live status is shown ML 2 a...

Страница 16: ...is added Here it is possible to set an alarm to for example Trip of GB Warning shutdown and so on Inhibits are also added in the protection pa rameter ML 2 application notes Converting PPU 2 to PPU 3 4189341126 UK Application and installation DEIF A S Page 16 of 18 ...

Страница 17: ...from a PPU 2 and a PPU 3 controller Parameter 7514 allows to enable PPU 2 Modbus addresses in a PPU 3 controller and has three different set tings 1 Standard Normal PPU 3 register layout 2 GPU PPU 2 GPU PPU 2 register layout Only GPU PPU 2 registers will respond requests to any other register will result in ILLEGAL DATA ADDRESS 3 MIX GPU PPU 2 register layout Requests to GPU PPU 3 registers that a...

Страница 18: ...ill occur A great variety of inputs can be selected such as digital inputs alarm conditions and running conditions A variety of the outputs can also be selected such as relay outputs change of genset modes and change of running modes ML 2 application notes Converting PPU 2 to PPU 3 4189341126 UK Application and installation DEIF A S Page 18 of 18 ...