S-run speed profile:
S-run speed profile is a stepwise safety run, where four extra steps are
defined with position and speed for each step.
Enabled: the configured speed profiled will be used whenever safety run is executed
Disabled: Only step zero (N S-run (step 0) will be executed.
The position of the resolver must be calibrated when using a speed profile. Calibration is done
placing the blade in position zero and using the Preset pos. function to set the number of resolver
revolutions to zero (see section
8.4.4 Configuring the CAN bus
Configure the CAN interface (se also section
Parameters:
•
Protocol:
Select the protocol to be used in the dropdown list
•
Baud rate:
It is recommended to use 250 kbps to avoid communication errors and processor load
•
CANopen, Base node ID:
Configure the node ID offset in Hexadecimal. The resulting address is
Base node ID+CAN ID switch position/value.
•
Prop.CAN, Rx ID:
Configure the receive address ID offset in Hexadecimal. The resulting address
is Rx ID+CAN ID switch position/value.
•
Prop.CAN, Tx ID:
Configure the transmit address ID offset in Hexadecimal. The resulting address
is Tx ID+CAN ID switch position/value
•
Time Out:
Recommended timeout is between 2 to 3 seconds, should be a higher than the
controller time out setting. Setting the timeout time to zero, disables the timeout function and no
error will be generated if the CAN/CANopen communication stops (at some point after
initialization)..
The
“CAN ID sw.” is for information only. It shows the state of the CAD ID switch on the IMD.
CANopen: If the Base node ID or CAN ID switch are changed, the IMD must be restarted. Se section
for details about the IMD behaviour when the Base node ID or ID switch are
changed.
8.4.5 Configuring the safe energy test
The purpose of the IMD safe energy test is to enable an external application to evaluate the state of
the safe energy source, in order to ensure that the safe energy source is able to provide the needed
energy at any time. Performing the test at regular intervals will enable timely replacement of the
source if the batteries or ultra-caps are bad.