IMD 100 Integration manual 4189360015 Rev. G
Units conversion
Page 179 of 243
10.3.4 Converting temperature Pt100 sensor (Pt1 to Pt4)
The temperature of a Pt100 sensor temperature in raw values can be read from any of the four Pt100
registers (see
), or CANopen objects 209C to 209F. In the following description, the actual
temperature read, is called
Actual_temp_raw
.
The following data is needed for the conversion (Temperature is in ºC):
Table 27
Raw temperature values Pt100
i
Raw_value
Temperature
1
57
-60
2
210
-50
3
362
-40
4
514
-30
5
590
-25
6
665
-20
7
816
-10
8
967
0
9
1117
10
10
1266
20
11
1341
25
12
1416
30
13
1564
40
14
1712
50
15
1860
60
16
2008
70
17
2081
75
18
2155
80
19
2301
90
20
2447
100
31
2593
110
32
2738
120
33
2810
125
34
2882
130
35
3027
140
36
3171
150
37
3314
160
38
3457
170