IMD 100 Integration manual 4189360015 Rev. G
IMD configuration
Page 120 of 243
o
T dc:
DC pre-magnetization time
o
V dc:
DC pre-magnetization start voltage
o
V min:
Minimum voltage at movement start
o
F min:
Minimum frequency at movement start
o
V corner:
Voltage at rated speed in percentage of the mains input
o
F corner:
Frequency at rated voltage. Use motor nominal frequency.
•
End (reserved for future use)
o
T dc:
-
o
V dc:
-
o
V min:
-
o
F min:
-
o
V corner:
-
o
F corner:
-
8.7
Configuring SE charger parameters (option)
The SE charger is a hardware option that can be ordered with the IMD. It is not possible to add it later.
The charger is an advanced multistage programmable charger, capable of optimised charging for
different types of supported energy sources. Refer to the IMD 100 function description for more
information about the charger.
8.7.1 Charger configuration management
Configuration can only be done when the charger is in Setup mode, which is done
with a “Setup
mode” button in the “SE charger” tab. Charging stops when the charger is in Setup mode, and starts
again automatically at the Bulk stage when the Setup mode is disabled.
Like other parameters of the IMD, the charger parameters configuration is done in the values stored in
the RAM. As soon as the Setup mode is disabled, it uses the parameter values from the RAM. Like
other IMD parameters, any values changed in the RAM, must be saved to EEPROM in order to be
used after restart, reset, or load of new parameters.
This is done in the “SE charger” tab, see IMD
Manager user manual for instructions.
It is also possible to configure the charger by executing a configuration script. The configuration script
can set the charger in setup mode configure all parameters, save all parameters to EEPROM and take
the charger out of setup mode.
8.7.2 Configuring the charger with a script
8.7.2.1 Prerequisites
•
A configuration script is available
•
Connect 3x400 V AC to the IMD mains terminals and turn on the power.
•
Connect the PC to the IMD with a USB cable and connect to the drive