4. Adjustment and control
As the instrument is linearized to a max. indication error of 0.5% corresponding to a
max. deviation of ±1.8° over the entire scale curve of 360°, it is not provided with an
adjustment device. For control of deflection (indication) as a function of input the table
below can be applied.
Single input:
Measuring
range
Input A
Input B
Disc position
in degrees
Clock position
of disc
4.00mA
0
12
8.00mA
90
3
12.00mA
180
6
16.00mA
270
9
4...20mA
(Disc moves
CW with posi-
tive input)
20.00mA
Not connected
360
12
0.00mA
0
12
0.25mA
90
3
0.50mA
180
6
0.75mA
270
9
0...1mA
(Disc moves
CW with posi-
tive input)
1.00mA
Not connected
360
12
-10.00V
0
12
-5.00V
90
3
0.00V
180
6
+5.00V
270
9
-10...0...10V
(Disc moves
CW with posi-
tive input)
+10.00V
Not connected
360
12
Double input (SIN/COS):
Measuring
range
Input A
SIN
Input B
COS
Disc position
in degrees
Clock position
of disc
12.0mA
20.0mA
0/360
12
20.0mA
12.0mA
90
3
12.0mA
4.0mA
180
6
4...20mA
4.0mA
12.0mA 270
9
0.5mA 1.0mA 0/360
12
1.0mA 0.5mA
90
3
0.5mA 0.0mA 180
6
0...1mA
0.0mA 0.5mA 270
9
0.0V
+10.0V
0/360 12
+10.0V
0.0V
90
3
0.0V
-10.0V 180 6
-10...0...10V
-10.0V 0.0V 270
9