5.3.4 Power supply and start
1
2
3
4
5
6
7
D
C
(
+
)
D
C
(
-)
N
o
t
u
se
d
E
m
e
rg
.
st
o
p
R
u
n
c
o
il
C
ra
n
k
D
+
Fuel
M
G
D+
B+
F1
F2
Fuses:
•
F1: 2 A MCB, c-curve
•
F2: 6 A MCB, c-curve
5.4 Communication
5.4.1 CAN bus power management system
1
9
2
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
8
2
9
3
0
3
1
3
2
P
M
S
H
i
P
M
S
S
h
P
M
S
L
o
AGC 150
AGC 150
AGC 150
120
120
P
M
S
H
i
P
M
S
S
h
P
M
S
L
o
P
M
S
H
i
P
M
S
S
h
P
M
S
L
o
Recommended cable: Belden 3105A or equivalent, 24 AWG (0.5 mm
2
) twisted pair, shielded, impedance 120 Ω, <40 mΩ/m, min. 95
% shield coverage.
INSTALLATION INSTRUCTIONS UK
Page 21 of 22