9
0
0
5.2 Using the voltage detector in an installation
After performing a functional test, the green light
"0"
illuminates indicating that the device is
ready for testing.
Note:
If PHEG1... voltage detectors are used, always connect the earth clamp before the test electrode.
Disassembly in reverse order.
Please note that voltage tests may only be performed when the
green lamp "0"
is lit up,
indicating that the voltage detector is ready for testing.
The status “ready for testing” applies for as long as the voltage detector is ready for operation.
After that, the device switches itself off automatically. If further tests are to be carried out,
press
the "TEST" button
again to perform a functional test.
The voltage detector is immediately ready for testing again. If
"voltage present"
is indicated, an
electronic lock prevents the device from automatically switching off during testing. After testing,
the device remains
ready for testing
(green light
"0" is illuminated
) for the period in which it
remains ready for operation.
Another functional test must be performed after testing.
functional test
ready for testing
battery replacement
Indication
Voltage/operating state
Permanent green light
No voltage present
Flashing red light
Voltage present
No light
Functional test not performed
(see 5.1)
Green and red lights flash simultaneously
Low battery (replace battery)
Fig. 5.1
Functional test
lamp " " "Test"
button Lamp "0"
lamp " " "Test"
button Lamp "0"
lamp " " "Test"
button Lamp "0"
Содержание 767610
Страница 13: ...13 Noter ...
Страница 27: ...13 Notes ...