Ensure that the voltage is 230V 50Hz. Also check that the model and capacity matches those of the in-
door unit. 

• 

Select a position for the outdoor unit which allows for the shortest possible unobstructed pipe length. 
Ensure that the air intake and discharge are unobstructed and that there is enough room for servicing.  

• 

Provide a concrete base or sturdy mounting plate and bolt the unit down using anti-vibration pads to 
reduce vibration and noise. 

• 

Due to the use of resilient, rubber compressor mountings, it is no longer necessary to remove the outer 
cover and loosen the compressor mounting nuts. 

• 

Two service valves are provided for ease of installation and servicing. They have gauge ports and 
Schrader valves. 

• 

Connect, evacuate and charge the unit in the following manner:- 
(a)  Connect the piping between the indoor and outdoor units. Use a drop of refrigerant oil when form-

ing the flares and ensure that they are without burrs and are of the correct shape and size. 

(b) Connect the suction and discharge gauges to the gauge ports and evacuate the piping and the indoor 

unit using a good vacuum pump. 

(c) When a low vacuum has been achieved, close the valves and the gauge manifolds and fully open 

the liquid and suction service valves with an allan key. 

(d) Test for leaks before operating the unit. 

NOTE:- The condensing unit has a full gas charge of R22 refrigerant which should be suffi-
cient for a back-to-back installation with 1/4” and 1/2” copper tubing. When the required in-
terconnecting  piping is more than 9m, an additional 20g/m of refrigerant must be added.  

(e) The additional refrigerant can be added either immediately after evacuation of the system or in va-

pour form when the unit is running. 

(f) 

Start up of the unit: 

Set the thermostat to the coldest position with the fan on maximum and push 

the Heating  / Cooling button. A 2.5 to 3.0 minute time delay will be experienced before the com-
pressor starts. 

(g) Run the unit and observe the pressures and temperatures. 

 

SERVICE TIP 

• 

The condensing temperature should be approximately 16°C to 18°C higher than the outdoor ambient 
temperature. The above should not be used as a charging method and is only a guide for new air-cooled 
split systems and air-cooled units with clean condensers and an unrestricted airflow. 

• 

Operate the unit using all functions i.e.; fan only, heating, cooling and at various fan speeds. Ensure 
that the unit operates efficiently and quietly. Disconnect the gauges and check that all the screws that 
were removed have been replaced. 

• 

Advise the customer how to operate the unit and explain the various features. 

 
 
 
 
 
 
 
 
 
 
 
 
 

Installation of the Outdoor unit 

Содержание 059 044

Страница 1: ...OLES CURTAIN WALL CONSOLES INSTALLATION INSTRUCTIONS Air conditioners CONSOLE The Manufacturer strives for continuous improve ments For this reason the text and illustrations in this book are subject...

Страница 2: ...sleeve slants outwards Weep holes at the lower edge allow rainwater to drain away freely Architectural and aesthetic requirements often necessitate the use of non standard louver assem blies As these...

Страница 3: ...eeve assembly Should the factory fitted condenser coil foam seals not butt up to the louver assembly insulated divider plates must be fitted to prevent hot air re circulation back into the condenser s...

Страница 4: ...unit from the electrical power supply b Remove the filter and the front access panel by removing the two screws at the bottom of the panel c Pull the 4 pin connector plug apart without unscrewing the...

Страница 5: ...and suction service valves with an allan key d Test for leaks before operating the unit NOTE The condensing unit has a full gas charge of R22 refrigerant which should be suffi cient for a back to back...

Страница 6: ...WIRING FOR EXTERNAL OVERLOAD COMPRESSOR O L Electrical Installation This appliance must be earthed and the manufacturer and the seller do not accept responsibility for any damage due to incorrect ins...

Страница 7: ...unting holes located on the Condenser Back Cover are now exposed and clearly visible Isolate the area and be sure not to contaminate the Electrical components with dust FRONT INLET GRILLE FILTER ASSEM...

Страница 8: ...ths and failure to comply with this condition shall render the warrant null and void 5 The Company shall not be responsible for damage to the product resulting from incorrect voltage or fault in the e...

Отзывы: