ADJUSTABLE PARAMETERS

 

(Factory default settings are shown in bold italicised text) 

 

Section

 

Parameter

 

Display shows

 

Values

 

Input settings 

Low Oil Pressure warning 

Oil pressure pre-alarm 

0-4bar (

1.17bar

 

Low Oil Pressure shutdown 

Oil pressure shutdown 

0-4bar (

1.03bar

 

High Temperature warning 

Coolant temp pre-alarm 

80-140

°

C (

115

°

C

 High 

Temperature 

shutdown

 

Coolant temp shutdown

 

80-140

°

C (

120

°

C

 Low 

Temperature 

warning 

Low Coolant  temp 

0-138

°

C (

64

°

C)

 

Timers 

Mains transient delay 

Mains transient delay 

0-30s (2s

 

Generator transient delay 

Gen transient delay 

0 -30s (0s

 

Start delay  

Start delay 

0 -10h (5s

 

Return delay  

Return delay 

0 -5h (30s

 

Preheat 

Preheat 

0 -5m (0s

 

Crank attempt 

Cranking time 

0 -60s (10s

 

Crank rest  

Crank rest  

0-60s (10s

 

Safety delay  

Safety on  

0-60s (10s

 

Overspeed overshoot  

Overspeed overshoot 

0-10s (2s

 

Warming up 

Warm up  

0-60m (0s

 

Transfer delay  

Transfer delay 

0-10m (0.7s

 

Cooling run 

Cooling  

0-60m (60s

 

Fail to stop delay 

Fail to stop 

0-2m (30s

 

Low battery volts delay 

Battery low delay 

0-24h (60s

 

High battery volts delay 

Battery high delay 

0-24h (60s

Mains (utility)  

Mains Low Voltage 

Mains undervolt trip 

50-360V ph-N (

184V

)

 

Mains High Voltage 

Mains overvolt trip 

50-360V ph-N (

276V

)

  

Mains Low Frequency 

Mains underfreq trip 

0-75Hz (

45Hz

 

Mains High Frequency 

Mains overfreq trip 

0-75Hz (

55Hz

Generator 

Generator Under voltage shutdown 

Gen low voltage shutdown 

50-360V ph-N (

184V

)

 

Generator Under voltage prealarm 

Gen low voltage prealarm 

50-360V ph-N (196V)

 

Generator Over voltage prealarm 

Gen high voltage prealarm 

50-360V ph-N (265V)

 

Generator Over voltage shutdown 

Gen high voltage shutdown 

50-360V ph-N (276V)

 

Generator Under frequency shutdown 

Gen low frequency shutdown 

0 -75Hz (40Hz

 

Generator Under frequency prealarm 

Gen low frequency prealarm 

0 -75Hz (42Hz

 

Generator Over frequency prealarm 

Gen high frequency prealarm 

0 -75Hz (55Hz

 

Generator Over frequency shutdown 

Gen high frequency shutdown 

0 -75Hz (57Hz

 

Generator delayed overcurrent 

Delayed high current 

100-200% (100%

Engine  

Underspeed (RPM) shutdown 

Underspeed shutdown 

0-6000RPM (1270

 

Underspeed (RPM) warning 

Underspeed prealarm 

0-6000RPM (1350

 

Overspeed (RPM) warning 

Overspeed prealarm 

0-6000RPM (1650

 

Overspeed (RPM) shutdown 

Overspeed shutdown 

0-6000RPM (1710

 

Overspeed overshoot % 

Overspeed overshoot 

0-10 (0%

 

Low DC Voltage 

Battery low warning 

0-40V (8V

 

High DC Voltage  

Battery high warning 

0-40V (33V

 

Charge Alternator Failure 

Charge fail warning 

0-39V (6V

Display 

Language 

Language 

ENGLISH

, OTHER  

 

 

 

ALTERNATIVE AC WIRING  

3 phase, 3 wire  
For other AC systems please consult the 
module operators manual 

ADJUSTABLE PARAMETERS

 

(continued) 

 

Section

 

Parameter

 

Display shows

 

Values

 

Application 

Engine speed selection 

Alternative Frequency  

Disable, Enable 

 

Volts selection 

Alternative Voltage 

Disable, Enable 

 

AC System 

AC System  

3 phase 4 wire 
Single phase, 2 wire 
3 phase, 3 wire 
2 phase 3 wire (L1 & L2) 
2 phase 3 wire (L1 & L3) 

 

Generator Full Load 

Generator full load 

0-6000A(500A)   

 

Droop control 

Droop 

Disable, Enable 

 

 

Droop 

0% (0%-5%) 

Compatible engine ECUs only 

 

Frequency Adjust 

Frequency Adjust 

Cummins CM850 only 

 

LCD Contrast 

Contrast 

†

           |           

„

 

 

Date/Time 

Date and Time 

dd mmm yyyy hh:mm 