Deep Sea Electronics Plc 5320 Скачать руководство пользователя страница 1

 

ACCESSING THE FRONT PANEL CONFIGURATION EDITOR

CONFIGURATION 

ENTER PIN 

**** 

 

Press the Stop/Reset 

 and Info 

 buttons 

simultaneously

 

 

If a module security PIN has been set, the PIN number 
request is then shown (The first * is flashing) :

 

 

 Press 

+

 or 

– 

buttons to adjust  it to the correct value. Press 

9

 

when the first digit is correctly entered. 

Repeat this process for the other digits of the PIN number. 

 When 

9

 is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not 

correct, the editor is automatically exited. To retry you must re-enter the editor as described above. 

CONFIGURATION 

Oil pressure pre-alarm 

 

If the PIN has been successfully entered (or the module PIN 
has not been enabled)  the first configurable parameter is 
displayed :

 

 

EDITING A PARAMETER 

 

2bar 30PSI 200kPa 

 

Enter the editor as described above.

 

CONFIGURATION 

Oil pressure pre-alarm 

2bar 30PSI 200kPa 

 Press 

the 

+

 and 

 buttons to cycle to the parameter you wish 

to change.

 

 Press 

the 

9

 button to enter edit mode. When in edit mode 

(indicated by the flashing parameter) pressing the

 

+

 and 

 

buttons will adjust the parameter to the desired value.

 

 

 For 

date and time editing only: press 

 to select between day, month, year, hours and minutes. 

 Press 

the 

9

 button to ‘save’ the value. The value will stop flashing to confirm that it has been saved. 

 

To select another value to edit, press the 

button. Continuing to press the 

+

 and 

 buttons will cycle 

through the adjustable parameters as shown overleaf. 

 

To exit the front panel configuration editor at any time, press the Stop/Reset 

 button. Ensure you 

have saved any changes you have made by pressing the 

9

 button first. 

 

NOTE:-  When the editor is visible, it is automatically exited after 5 minutes of inactivity to 

ensure security. 

 

NOTE:-  The PIN number is automatically reset when the editor is exited (manually or 

automatically) to ensure security. 

 

NOTE:- More comprehensive module configuration is possible using the 5xxx series PC 

configuration software in conjunction with the P810 PC interface. Please contact us for further 
details. 

 
 

 

D E E P   S E A   E L E C T R O N I C S    

5 3 2 0   I N S T A L L A T I O N   I N S T R U C T I O N S

 

053-014 

ISSUE4 

Deep Sea Electronics Plc.

Highfield House, Hunmanby Industrial Estate, 

North Yorkshire. YO14 0PH.  

ENGLAND 

Tel:+44 (0)1723 890099.  

Fax: +44 (0)1723 893303. 

LO CALL (from UK BT landlines) : 

Telephone 0845 260 8900. Fax 0845 260 8901 

Email: [email protected]  

Web: www.deepseaplc.com

 

Deep Sea Electronics inc. 

3230 Williams Avenue 

Rockford, Illinois 61101-2668,  

U.S.A. 

Phone: +1 (815) 316-8706.  

Fax: +1 (815) 316- 8708 

TOLL FREE (USA only) : Tel: 1 866 636 9703 

Email: [email protected] 

Web: www.deepseausa.com 

DIMENSIONS

 :

  

240mm x 172mm x 57mm 

(9.5” x 6.8” x 2.25”) 

PANEL CUTOUT

 : 220mm x 160mm  

(8.7” x 6.3”)

TYPICAL WIRING DIAGRAM 