Factory setting values
Burner model - Boiler power Output
P (bar (MPa))
(1)
U (%)
Indicative setting
(2)
CO
2
(%) Head pressure
(mbar)
Indicative setting
F10E2-5.30 - 30 kW boilers
E
Minimum output 7 (0,7)
29
12,5
3,6
Z
Start-up output
15 (1,5)
65
13,2
6,2
A
Maximum output 22 (2,2)
91
13,2
8,6
(1) Fuel oil pressure
(2) Fan rotation speed
6.4.3.
Checking combustion
The check on combustion is done by measuring the percentage of
CO
2
in the flue gas discharge flue. To do this, proceed as follows:
1. Unscrew the plug of the flue gas measurement point.
2. Connect the flue gas analyser.
CAUTION
Ensure that the opening around the sensor is completely
sealed when taking measurements.
3. Measure the CO
2
level in the flue gases.
4. Fill in the table below with the values measured.
Measured values P(bar) U(%) CO
2
(%)
Minimum output
Start-up output
Maximum output
5. If the CO
2
level does not match the required value, correct the ratio
of the fan rotation speed U.
¼
See chapter: "Setting the burner’s 3 operating outputs",
C003280-B
AFC 18 - AFC 24 - AFC 30
6. Commissioning
09/07/2015 - 300026439-07
101