User and Installation Manual
Control panel & Control PCB
Inicontrol 2
Страница 1: ...PROJECT INNOVENS PRO Ireland en User and Installation Manual Control panel Control PCB Inicontrol 2...
Страница 2: ...ced parameters 17 5 3 Carrying out an auto detect 18 5 4 Restoring to factory settings 18 5 5 Chimney sweep mode forced full load or part load 19 5 6 Connected control PCBs 20 5 7 Activating the manua...
Страница 3: ...9 2 1 Reading out the Error memory 32 9 2 2 Clearing the error memory 32 Contents 7667004 v 01 12072017 3...
Страница 4: ...for the installation and initial commissioning of the appliance The installer must ob serve the following instructions Read and follow the instructions given in the manuals provided with the applianc...
Страница 5: ...Have the required inspections and maintenance car ried out by a qualified installer Keep the instruction manuals in good condition close to the appliance 1 Safety 7667004 v 01 12072017 5...
Страница 6: ...ention to special instructions We do this to improve user safety to prevent problems and to guarantee correct operation Caution Risk of material damage Important Please note important information See...
Страница 7: ...ue 3 DHW temperature Access to set temperature Plus key Raising the value 4 CH DHW function Toggles function ON OFF Enter key Confirms selection or value 5 Chimney sweeping keys Important Press the 1...
Страница 8: ...three way valve is connected The circulation pump is turning ECO mode operation is enabled Switch the appliance off then on again 3 2 Expansion board description The expansion board SCB 01 has the fol...
Страница 9: ...enu User menu Installer Menu Manual mode menu Failure Menu Hour Run Meters Timer Program Clock menu PCB menu 1 1 The icon is displayed only if an optional control PCB has been instal led 3 Press the k...
Страница 10: ...he selection 5 Keep pressing the key until is displayed 6 Press the key to confirm the parameter 7 Keep pressing the key until the required language code is dis played 8 Press the key to confirm the c...
Страница 11: ...ture The central heating flow temperature can be raised or lowered separately from the heating requirement 1 Press the key to select the central heating flow temperature 2 Press the key to access the...
Страница 12: ...to lower the heating temperature during the night or an absence during the day A start and end time for the lower temperature can be set in the Timer Program Note Activate the timer program using the...
Страница 13: ...mfort temperature 8 Press the key to confirm the selection 9 Select the status C1 corresponding with the switch time S1 by press ing the or key Tab 5 Statuses C1 to C6 for the periods S1 to S6 C1 to C...
Страница 14: ...e installer Important First select a device control PCB or zone to view or amend a set ting Caution Modification of the factory settings may impair operation of the de vice control PCB or zone 1 Navig...
Страница 15: ...alue 8 Press the key to confirm the value 9 Press the h key multiple times to go back to the main display Fig 49 Step 7 MW 3000334 01 Fig 50 Step 8 MW 3000335 01 Fig 51 Step 9 MW 3000311 01 4 User ins...
Страница 16: ...he code is displayed 4 Press the key to confirm opening the menu 5 Keep pressing the key until the required device control PCB or zone is displayed 6 Press the key to confirm the selection 7 Keep pres...
Страница 17: ...code is displayed 4 Press the key to confirm opening the menu 5 Keep pressing the key until the required device control PCB or zone is displayed 6 Press the key to confirm the selection 7 Keep pressin...
Страница 18: ...6 Press the key to confirm the selection 7 Keep pressing the key until is displayed 8 Press the key to carry out the auto detect 9 After a while the main display is shown auto detect is complete 5 4...
Страница 19: ...to confirm the value The factory settings are reset The display shows various informa tion and returns to the main display after 3 minutes 5 5 Chimney sweep mode forced full load or part load 1 Press...
Страница 20: ...e for example when the controller has not yet been connected 1 Navigate to the manual mode menu 2 Press the key to open the menu 3 Press the or keys to modify the required flow temperature in manual m...
Страница 21: ...roduction 3 Press the key to confirm the selection of DHW production 4 Press the key to change the current status of DHW production 5 Press the key to confirm the changed status DHW production is swit...
Страница 22: ...ters SCB 01 page 28 5 10 Reading out current values 1 Navigate to the Information menu 2 Press the key to open the menu 3 Keep pressing the key until the required device control PCB or zone is display...
Страница 23: ...meter version See Other manuals for more values For more information see Signals SCB 01 page 28 5 11 Status and Sub status The information menu gives the Status and Sub status numbers For more informa...
Страница 24: ...pend ing on the make and type of pump the pump can be controlled by a 0 10 V or a signal The speed of the pump is modulated based on the signal re ceived from the boiler Connect the system pump contro...
Страница 25: ...ve set point 5 After 4 minutes the second boiler stops running if T 6K and the system temperature is still more than 3 C above set point 6 After 8 minutes the third boiler stops running if T 6K and th...
Страница 26: ...NP EM platform related parameters OP Oil fired related parameters PP CH parameters 8 1 1 Description of the parameters Inicontrol 2 Tab 9 Factory settings Code Display text Description Range Inicontr...
Страница 27: ...erved 7 Service request 8 Boiler on Central Heating 9 Boiler on Domestic Hot Water 10 Central Heating pump on 11 Locking or Blocking 0 Tab 11 Mandatory platform Code Display text Description Range SCB...
Страница 28: ...ting 0 Off 1 On AM201 Status contact 1 Status of status contact 1 The meaning is dependant on the current function setting 0 Off 1 On Tab 15 Mandatory platform Value Display text Description Range AM0...
Страница 29: ...nual Heat demand Central heating On 16 Boiler Frost Protection 17 DeAiration 18 Control unit Cooling 19 Reset In Progress 20 Auto Filling 21 Halted 200 Device Mode Tab 18 Sub status numbers Sub status...
Страница 30: ...38 ColdStart 39 ChResume 40 RemoverBurnerOnSuRequest 41 FanToPostPurge 42 OpenExtGasAndFlueGasValveRelay 43 BurnerStopFanToFLueGasValveRpm 44 StopFan 45 LimitedPowerOnTflueGas 60 PumpPostRunning 61 Op...
Страница 31: ...cking occurs as a result of an error The control panel shows the block ing code as follows The symbol The code for example Important The appliance starts up again automatically only when the cause of...
Страница 32: ...details 9 Press the h key multiple times to go back to the main display 9 2 2 Clearing the error memory 1 Navigate to the Error menu 2 Press the key to open the menu 3 Keep pressing the key until the...
Страница 33: ...nu is dis played 6 Press the key to delete the errors from the error memory 7 Press the h key to go back to the main display Fig 136 Step 5 MW 3000375 01 Fig 137 Step 6 MW 3000376 01 Fig 138 Step 7 MW...
Страница 34: ...9 Troubleshooting 34 7667004 v 01 12072017...
Страница 35: ...nological information contained in these technical instructions as well as any drawings and technical de scriptions supplied remain our property and shall not be multiplied without our prior consent i...