20
IMPORTANT INFORMATION FOR INSTALLATION
s
tatutOry
guidelines
fOr
installatiOn
and
maintenance
Installation and maintenance of the appliance must be performed
by a qualified professional in accordance with the relevant statutory
guidelines and good industry practice.
p
OsitiOn
The dimensions given are the minimum recommended (in mm) to
ensure sufficient access around the boiler.
Note:
for installations with several boilers in cascade configuration,
these same dimensions must be observed for each boiler.
INNOVENS PRO MCA 160 boilers are installed in accordance with
the rules for installation in dedicated boiler rooms outside of the
inhabited area. The installation rules for the terminals (horizontal or
vertical) must also be observed - see page 29.
MCA_F0082
600
30
30
min. 1000
600
min.
500
min.
300
1045
min. 1000
MC
A_F0082
In order to avoid damage to the boilers, it is necessary to prevent the contamination of combustion air by chlorine and/
or fluoride compounds, which are particularly corrosive.
These compounds are present, for example, in aerosol sprays, paints, solvents, cleaning products, washing products,
detergents, glues, road grit, etc.
The following must therefore be ensured:
- Preventing the intake of air expelled by premises using such products: hairdressing salons, dry cleaners, industrial premises (solvents),
premises containing refrigeration systems (risk of refrigerant leakage), etc.
- Preventing such products from being stored close to boilers.
We would like to underline that, should the boiler and/or peripheral equipment be corroded by chlorine and/or fluoride
compounds, the contractual guarantee will be invalidated.
Room ventilation
Comply with local regulations.