![DeDietrich GT 530-10 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/dedietrich/gt-530-10/gt-530-10_installation-and-service-manual_2462454012.webp)
12
GT 530
25/01/2012 - 300011906-001-D
3.3.3
Boilers for following countries: Switzerland
Conditions of use:
Maximum operating pressure: 6 bar
Maximum operating temperature: 100 °C
Boiler thermostat setting: 30 to 90°C
Safety thermostat setting: 110 °C
*Maintenance consumption: total heat emission when the burner is
off as a percentage of the nominal input power when the difference
between the mean boiler temperature and the room temperature is
30 K - in accordance with DIN 4702 - EN 303.
Boiler
GT
530
-8
GT
530
-9
GT
530
-10
GT
530
-11
GT
530
-12
GT
530
-13
GT
530
-14
GT
530
-15
GT
530
-16
GT
530
-17
GT
530
-18
GT
530
-19
GT
530
-20
GT
530
-21
GT
530
-522
GT
530
-23
GT
530
-24
GT
530
-525
Useful output
kW
250
to
365
275
to
395
300
to
435
330
to
470
360
to
510
390
to
550
420
to
580
440
to
620
470
to
660
495
to
690
530
to
730
550
to
770
580
to
810
610
to
840
640
to
880
670
to
920
690
to
960
720
to
1000
Power input
kW
260
to
390
291
to
425
315
to
465
346
to
495
381
to
550
409
to
590
440
to
620
460
to
650
492
to
710
519
to
740
557
to
785
578
to
825
609
to
870
642
to
905
679
to
945
705
to
990
728
to
1030
764
to
1075
Number of sections
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Water content
l
427
465
503
541
579
617
655
693
731
769
807
845
905
943
981
1019
1057
1095
Water resistance
(1)
∆
T = 10K
mbar
13.9
15.8
19.1
23.1
27.6
32.2
35.2
40.3
15.7
17.1
19.3
21.5
23.4
25.1
28.0
30.2
32.1
37.0
∆
T = 15K
6.2
7
8.5
10.3
12.3
14.3
15.7
17.9
7
7.6
8.6
9.5
10.4
11.2
12.4
13.3
14.5
16.5
∆
T = 20K
3.5
4.2
5.1
5.7
6.7
7.7
8.8
10
3.8
4.1
4.6
5.1
5.6
6.1
7.6
7.8
8.2
9.3
Pressure in the furnace for nozzle
pressure = 0
(4)
mbar
1.05
1.05
1.1
1.1
1.15
1.2
1.2
1.25
1.3
1.3
1.35
1.4
1.5
1.5
1.55
1.6
1.6
1.65
Flue gas temperature - Ambient
temperature
(1) (3)
K
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
<160
Mass flue gas flow
rate
(1) (2)
Fuel oil
kg
per
sec
0.160 0.174 0.191 0.203 0.226 0.242 0.254 0.267 0.291 0.304 0.322 0.339 0.357 0.371 0.388 0.406 0.423 0.441
Gas
0.174 0.190 0.207 0.221 0.245 0.263 0.276 0.290 0.316 0.330 0.350 0.367 0.388 0.403 0.421 0.441 0.459 0.479
Combustion
chamber
Inscribed
diameter
mm
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
614
Equivalent
diameter
mm
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
694
Depth
mm
817
928
1039
1150
1261
1372
1483
1594
1705
1816
1927
2038
2189
2300
2411
2522
2633
2744
Volume
m
3
0.32
0.36
0.40
0.45
0.49
0.53
0.57
0.61
0.65
0.70
0.74
0.78
0.84
0.88
0.92
0.96
1.00
1.05
Maintenance
consumption*
∆
T = 30K
%
0.13
0.12
0.12
0.11
0.11
0.11
0.11
0.10
0.10
0.10
0.10
0.10
0.10
0.09
0.09
0.09
0.09
0.09
Weight (empty)
kg
2046
2237
2412
2601
2810
3000
3171
3364
3561
3756
3955
4124
4343
4538
4734
4930
5107
5297
(1)
Nominal operation (top boiler power)
(2)
CO
2
= 13.1 to 13.5% with fuel oil and 9.5% with natural gas.
(3)
Boiler temperature: 80 °C
Ambient temperature: 20 °C
(4)
In order for the boiler to operate correctly, it is
imperative to respect the draught at the nozzle.
Содержание GT 530-10
Страница 1: ...GT 530 Fuel oil gas boilers Installation and Service Manual 300011906 001 D EN ...
Страница 30: ...30 GT 530 25 01 2012 300011906 001 D Insulation 71 70 M000050 ...
Страница 31: ...31 25 01 2012 300011906 001 D GT 530 Casing ...
Страница 37: ...37 25 01 2012 300011906 001 D GT 530 ...
Страница 38: ...38 GT 530 25 01 2012 300011906 001 D ...
Страница 39: ...39 25 01 2012 300011906 001 D GT 530 ...