Wiring Legend
L – Main Line 120v
N – Main Neutral
N – Burner Neutral
L1 – Burner Line 120v
T1 – Boiler Limit
T2 – Burner Limit
T6 – Boiler Operating Limit
T7 – Burner Low Fire – As Required
T8 – Burner Hi Fire
S3 – Optional Burner Alarm
VA – Optional Hi Temp Alarm
A1-A2 – Optional Alarm Device
[Supplied by Others]
J1-J2 – Field Supplied jumpers
ALL ELECTRICAL CONNECTIONS
MAYBE FROM MULTIPLE SOURCES
Application Note for BMS or BAS systems:
The Local-Remote switch or enable/disable forced relay,
must interrupt the TCH2 control . TheTS & TCH1 limits
must remain in the limit circuit.
WARNING – CAUTION:
Panel Wiring Options:
On-Off Control [Single stage burners]
use jumper as shown
2 Stage Control [2 Stage burners]
Remove jumper 2 install firing rate control from burner
T6 – T8
Progressive Modulating Control
[Multi-Stage burners]
Remove jumpers 1
Installed burner limit circuit between T1 & T2
Remove jumper 2
Install burner firing rate control between T6 [common]
T7 [min rate] & T8 [max rate]
Consult burner manufacturer:
All burner wiring
Modulating Signal and required Controls
Burner Motor May require additional
power source
BMS Local-Remote Control Wiring.
Flexible Eutectic Sales Ltd. [De Dietrich North America] FA 122 Panel – Boiler Controller
12
11
10
9
8
7
6
VA
S3
T8
T7
T6
T2
T1
1
6
3
N
120v 60Hz.
L1
5
N
4
TCH
2
2
4
C
TCH
1
2
1
C
TS
1
2
C
2
7
8
9
12
4
11
A1
A2
In
te
rnal
L
Burner Power
L
N
Limit Circuit
Firing Rate Circuit
Burner Connections
J1
J2
T1
T2
T6
T7
T8
10
5
L
N
Vent Safety
Device
Auxiliary Hi-
Limit [Optional]
LWCO
Service
Switch
Fused
Disconnect
Main fuse
disconnect
6A 120V max
Service Switch
[Others]
LWCO
Device
[As required]
Burner Safety
Interlock –
Optional [Others]
Wiring Symbols
Auxiliary limit –
Optional [Others]
120V Alarm
indicator [Others]
Factory Wiring
Field Wiring
[Others]
Strain Relief
[Others]
Alarm Wiring
[Others]
Jumper Wiring
[Others]
Vent Safety
Device [NC]
1
7
06/10/06 - 94863873 - 85534150E
GT 300 A/II
Boiler Control Wiring
Содержание GT 300 A
Страница 24: ...BASE FRAME INSULATION 24 GT 300 A II 06 10 06 94863873 85534150E...
Страница 25: ...CASING 25...
Страница 29: ......
Страница 30: ...30 GT 300 A II 06 10 06 94863873 85534150E...
Страница 31: ...31...
Страница 32: ...www dedietrich boilers com www dedietrichthermique com...
Страница 37: ...5 31 08 06 ND GT 300 A II 1 FD30 FD31 FD32 FD33 FD34 FD35 2...
Страница 38: ...6 GT 300 A II 31 08 06 ND 3 4...
Страница 39: ...7 31 08 06 ND GT 300 A II 5 1 Glasspaper 6 2 Lubricant supplied 8553N051A...
Страница 40: ...8 GT 300 A II 31 08 06 ND 7 8 3 Tube of silicon caurk provided 8553N012 3 8553N128A 1...
Страница 41: ...9 31 08 06 ND GT 300 A II 9 1 Thermocord 10...
Страница 42: ...10 GT 300 A II 31 08 06 ND 11 12...
Страница 43: ...11 31 08 06 ND GT 300 A II 13 1 Glasspaper 2 Lubricant supplied B 1...
Страница 44: ...12 GT 300 A II 31 08 06 ND 14 15 Adjust the thermal insulation to match the burner 7 1 2...
Страница 46: ...14 GT 300 A II 31 08 06 ND 18 19...
Страница 47: ...15 31 08 06 ND GT 300 A II 20 Desludging unit connection 8553N172...
Страница 50: ...18 GT 300 A II 31 08 06 ND 23 24 M8 4x 8553N028...
Страница 51: ...19 31 08 06 ND GT 300 A II 25 A Thermocord 26...
Страница 56: ...24 GT 300 A II 31 08 06 ND 31 8 9 section boilers 8553N116A...
Страница 57: ...25 31 08 06 ND GT 300 A II 32 8553N117...
Страница 58: ...26 GT 300 A II 31 08 06 ND 33 34 8553N118 M12 M12 M12 M12...
Страница 59: ...27 31 08 06 ND GT 300 A II 35 1 3 3 2 8553N119A 1 M8 M8 4 M8...
Страница 60: ...28 GT 300 A II 31 08 06 ND 36 37 8553N120 1 2 2 2 8553N121A...
Страница 61: ...29 31 08 06 ND GT 300 A II 38 120 V 60 Hz 8553N173...
Страница 62: ...30 GT 300 A II 31 08 06 ND 39 Control panel assembly 40 8553N174 8553N0 54A 1 2 2...
Страница 64: ...32 GT 300 A II 31 08 06 ND 44 8553N124...
Страница 65: ...33 31 08 06 ND GT 300 A II 45 8553N126 1 2 2 1...
Страница 66: ...34 GT 300 A II 31 08 06 ND 46 A Stick warning label B Stick data plate A B...
Страница 67: ...35 31 08 06 ND GT 300 A II...