01/03/07 - 94858596 - 8502-4590A
Adaptation à un autre gaz - GZ350 - DTG 220/II - DTG 230
7 Pressure settings and calibrated injector markings
7.1 Version S
(1)
15 °C - 1013 mbar
7.2 Version Eco.NOx
(1)
15 °C - 1013 mbar
Boilers DTG 220-... S/II
Boilers DTG 230-... S
7
8
9
10
11
12
13
14
Useful output
Stage1
kW
26
33
33
40
40
47
47
47
Stage2
kW
52
59
66
72
80
88
94
100
Power input
Stage1
kW
28.5
36.1
36.1
43.6
43.6
51.2
51.2
51.2
Stage2
kW
56.9
64.5
72.1
78.6
87.2
95.8
102.3
108.7
Nozzle pressure
GZ350
mbar
7.6
7.6
6.8
6.4
6.4
6.7
6.1
5.7
Start-up pressure
GZ350
mbar
5
5
5
5
5
5
5
5
Nozzle
Number of nozzles
6
7
8
9
10
11
12
13
GZ350
365B
365B
365B
365B
365B
365B
365B
365B
Gas flow rate - Stage2
GZ350
m
3
/h
(1)
8.37
9.49
10.61
11.56
12.82
14.09
15.04
15.99
Boilers DTG 220-... Eco.NOx/II
Boilers DTG 230-... Eco.NOx
6
7
8
9
10
11
12
13
14
Useful output
Stage1
kW
26
26
33
33
40
40
47
47
47
Stage2
kW
43
52
59
66
72
80
88
94
100
Power input
Stage1
kW
28.5
28.5
36.1
36.1
43.6
43.6
51.2
51.2
51.2
Stage2
kW
47.1
56.9
64.5
72.1
78.6
87.2
95.8
102.3
108.7
Nozzle pressure
GZ350
mbar
7.3
7.6
7.6
6.8
6.4
6.4
6.7
6.1
5.7
Start-up pressure
GZ350
mbar
5
5
5
5
5
5
5
5
5
Nozzle
Number of nozzles
5
6
7
8
9
10
11
12
13
GZ350
365B
365B
365B
365B
365B
365B
365B
365B
365B
Gas flow rate - Stage2
GZ350
m
3
/h
(1)
6.93
8.37
9.49
10.61
11.56
12.82
14.09
15.04
15.99