L Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
Tab.24 Maximum length in the various pressure zones
C 330 ECO
Maximum length L (in metres)
Ø 250 mm
280
50
350
50
430
50
500
50
570
49
650
40
(1) Calculated with rigid tube and 90° bend and discharge without cover ( "free"
opening)
L Total length of the flue gas outlet and air supply duct
Connecting the flue gas outlet
Connecting the air supply
Tab.25 Maximum length in the various pressure zones
C 630 ECO
Maximum length L (in metres)
Ø 350 mm
Ø 400 mm
560
50
50
700
50
50
860
50
50
1000
33
50
1140
—
22
1300
—
—
(1) Calculated with rigid tube and 90° bend and discharge without cover ( "free"
opening)
Reduction table
Tab.26 Pipe reduction for each element used
Diameter
Pipe reduction (in metres)
45° bend
90° bend
150 mm
1.2
2.1
180 mm
1.4
2.5
200 mm
1.6
2.8
250 mm
2.0
3.5
300 mm
2.4
4.2
350 mm
2.8
4.9
400 mm
3.2
5.6
6.4.4
Additional guidelines
Installation
For installing the flue gas outlet and air supply materials, refer to the
instructions of the manufacturer of the relevant material. After
installation, check at least all flue gas outlet and air supply parts for
tightness.
Fig.23
Various pressure zones C 330 ECO
AD-0000558-01
L = +
Fig.24
Various pressure zones C 630 ECO
AD-0000559-01
L = +
6 Installation
7600532 - v.11 - 13122018
35