Tab.6
Cooling mode: outdoor air tempe35°C, water temperature at the 18°C. Stated performances at nominal
load in accordance with EN 14511-2.
Measurement type
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP
11 MR-2
AWHP
11 TR-2
AWHP
16 MR-2
AWHP
16 TR-2
AWHP
22 TR–2
AWHP
27 TR–2
Cooling output
kW
3.80
4.69
7.90
11.16
11.16
14.46
14.46
17.65
22.20
Energy efficiency ratio
(EER)
-
4.28
4.09
3.99
4.68
4.68
4.43
4.43
3.80
3.80
Absorbed electrical
power
kWe
0.89
1.15
2.00
2.35
2.35
3.65
3.65
4.65
5.84
Tab.7
Common specifications
Measurement type
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP
11 MR-2
AWHP
11 TR-2
AWHP
16 MR-2
AWHP
16 TR-2
AWHP
22 TR–2
AWHP
27 TR–2
Total dynamic head at
nominal flow rate
kPa
62
61.80
49.30
39.30
39.30
21.30
21.30
-
-
Nominal air flow rate
m
3
/h
2680
2700
3000
6000
6000
6000
6000
8400
8400
Power voltage of the
outdoor unit
V
230
230
230
230
400
230
400
400
400
Start-up amperage
A
5
5
5
5
3
6
3
-
-
Maximal amperage
A
12
13
17
29.5
13
29.5
13
19
21
Sound power - In
dB(A) 43
43
51
51
51
51
51
43
43
Acoustic power - Out
dB(A) 58
65
65
69
69
69
69
77
77
R410A refrigerant
kg
1.4
1.3
3.2
4.6
4.6
4.6
4.6
7.1
7.7
R410A refrigerant
tCO
2
e 2.923
(2.694)
2.714
(2.501)
6.682
(6.157)
9.605
(8.850)
9.605
(8.850)
9.605
(8.850)
9.605
(8.850)
14.825
(13.660)
16.078
(14.815)
Refrigerant connec
tion (Liquid - Gas)
inch
1/4 - 1/2 1/4 - 1/2 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 - 5/8 3/8 - 1 or
3/8 -
3/4
1/2 - 1 or
1/2 -
3/4
Maximum precharged
length
m
7
10
10
10
10
10
10
30
30
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 55 °C.
(2) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 45 °C
for AWHP 4.5 MR only (inner and outer sides).
(3) The quantity of refrigerant in tonnes of CO
2
equivalent is calculated using the following formula: quantity (in kg) of refrigerant x GWP/
1000. The Global Warming Potential (GWP) of the R410A is 2088 following the IPCC fourth assessment report (1924 following IPCC
fifth assessment report).
(4) Warning: the refrigerant connection lengths are limited to 20 m with the 3/4" gas pipe.
3.3.2
Heat pump weight
Tab.8
Indoor unit
Indoor unit
Unit
MIT-S 4-8/E
MIT-S 4-8/H
MIT-S 11-16/E MIT-S 11-16/H MIT-S 22-27/E MIT-S 22-27/H
Net weight
kg
59
53
66
60
66
60
Gross weight kg
70
64
77
71
77
71
Tab.9
Outdoor unit
Outdoor unit
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP
11 MR-2
AWHP
11 TR-2
AWHP
16 MR-2
AWHP
16 TR-2
AWHP
22 TR–2
AWHP
27 TR–2
Weight
kg
54
42
75
118
130
118
130
135
141
3 Technical specifications
10
MIT-S