Parameter
Description
Unit
Domestic hot water production mode:
= programming
= manual
= frost protection mode
X
Heat pump flow temperature
°C
X
Heat pump return temperature
°C
X
System flow temperature.
°C
X
Heating temperature set point
°C
Software version for the selected PCB
X
X
Parameter version for the selected PCB
X
X
Tab.30 Values available (X) in the
sub-menu
Parameter
Description
Software version
X
X
Parameter version
X
X
6.3.1
Control system sequence
Tab.31 List of statuses and sub-statuses
Status (parameter
)
Sub-status (parameter
)
= off
= total system shut-down
= heating / cooling / domestic hot water
demand
= off
The set point is reached. The compressor can start up whenever necessary.
= anti-short cycle
The heating set point has been reached. The compressor is not authorised to
restart.
= reversal valve switch to heating position
= power supply to the hybrid pump
= pending start-up conditions on the heat pump and the back-ups
= three-way valve switch to domestic hot water position
6 Settings
7623755 - v05 - 27042017
MIV-4
45