3.2
Technical data
3.2.1
Conditions of use
Tab.3
Pressure limitations
Maximum operating pressure of the heating circuit
0.3 MPa (3 bar)
Maximum operating pressure of the collector circuit
0.3 MPa (3 bar)
Tab.4
Temperature limitations
Limit operating temperatures on the heating circuit in Heating mode
+7°C / +80°C
Limit operating temperatures on the heating circuit in Cooling mode
+7°C / +25°C
Limit operating temperatures on the collection circuit (source)
-15 °C / +35 °C
3.2.2
Heat pump
Tab.5
Performances for a glycol water/water system (0°C/-3°C and 30°C/35°C), in accordance with NF EN 14511–1
Measurement
type
Unit
GSHP 5
MR-E
GSHP 5
TR-E
GSHP 9
MR-E
GSHP 9
TR-E
GSHP
12 MR-E
GSHP
12 TR-E
GSHP
15 TR-E
GSHP
19 TR
GSHP
27 TR
Power supply
V
(~50 Hz)
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
400
three-
phase
400
three-
phase
400
three-
phase
Coefficient of
performance
(COP)
4.12
4.12
4.13
4.13
4.09
4.09
4.23
4.04
4.04
Absorbed elec
trical power
kW
1.38
1.38
2.39
2.39
3.10
3.10
4.04
5.05
7.25
Application flow
rate
m
3
/h
0.98
0.98
1.70
1.70
2.18
2.18
2.95
3.52
4.83
Heat output
kW
5.70
5.70
9.88
9.88
12.66
12.66
17.09
20.40
27.99
Tab.6
Performances for a glycol water/water system (0°C/-3°C and 40°C/45°C), in accordance with NF EN 14511–1
Measurement
type
Unit
GSHP 5
MR-E
GSHP 5
TR-E
GSHP 9
MR-E
GSHP 9
TR-E
GSHP
12 MR-E
GSHP
12 TR-E
GSHP
15 TR-E
GSHP
19 TR
GSHP
27 TR
Power supply
V
(~50 Hz)
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
400
three-
phase
400
three-
phase
400
three-
phase
Coefficient of
performance
(COP)
3.31
3.31
3.43
3.43
3.42
3.42
3.53
3.43
3.28
Absorbed elec
trical power
kW
1.63
1.63
2.74
2.74
3.57
3.57
4.63
5.84
8.17
Heat output
kW
5.39
5.39
9.41
9.41
12.21
12.21
16.35
20.05
26.82
3 Technical specifications
7611407 - v07 - 14022022
GSHP
11