Measure
ment type
Unit
AWHP 4.5
MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Acoustic
power - In
side
dB(A)
49
49
49
48
48
48
48
Acoustic
power -
Outside
dB(A)
61
65
67
69
69
70
70
Refrigerant
fluid R410A
kg
1.3
1.4
3.2
4.6
4.6
4.6
4.6
R410A re
frigerant
tCO
2
e
2.714
2.923
6.680
9.603
9.603
9.603
9.603
Refrigerant
connection
(Liquid -
Gas)
inch
1/4 - 1/2
1/4 - 1/2
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
3/8 - 5/8
Max. pre-
charged
length
m
7
10
10
10
10
10
10
(1) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7°C, water 55°C
(2) Noise radiated by the envelope - Test run in accordance with the NF EN 12102 standard, temperature conditions: air 7 °C, water 45 °C
for AWHP 4.5 MR only (inner and outer sides).
(3) Quantity of refrigerant calculated in tonnes of CO
2
equivalent
Important
The values in tonnes of CO
2
equivalent are calculated using the
following formula: quantity (in kg) of refrigerant fluid x GWP /
1000.
The Global-Warming Potential (GWP) of R410A gas is 2088.
3.2.2
Domestic hot water tank
Tab.8
Technical specifications primary circuit (heating water)
Specification
Unit
Value
Maximum operating temperature
Version with hydraulic back-up
°C
90
Minimum operating temperature
°C
7
Maximum operating pressure
MPa (bar)
0.3 (3.0)
Exchanger capacity
Litres
11.3
Exchange surface
m²
1.7
Tab.9
Technical specifications secondary circuit (domestic water)
Specification
Unit
Value
Maximum operating temperature
°C
80
Minimum operating temperature
°C
10
Maximum operating pressure
MPa (bar)
1.0 (10.0)
Water capacity
Litres
177
3 Technical specifications
18
200 ESL HYBRID
7613346 - v06 - 02072019