background image

 

Instruction manual 

 

Negative pressure unit 

 

Compact 25.000

 

 
 
 
 
 

 

 
 
 
 
 
Manufacturer: 

 

deconta  GmbH 

 

 

 

 

Im Geer 20, D - 46419 Isselburg 

 
Description / Type-No.: 

Compact 25.000  /  

Type  524, 532 

Содержание Compact 25.000

Страница 1: ...Instruction manual Negative pressure unit Compact 25 000 Manufacturer deconta GmbH Im Geer 20 D 46419 Isselburg Description Type No Compact 25 000 Type 524 532...

Страница 2: ...cabinet 7 5 4 Filter description Classification 7 5 5 Information for filter change 9 6 Technical data 10 6 1 Fan guide line 10 6 2 Performance data 11 6 3 Filter system 11 6 4 Connections Dimensions...

Страница 3: ...antee Stability Long life and aptness on site Mechanics with kick Pleasing design The copyright of this instruction manual remains with deconta This manual is intended for assembly operation and maint...

Страница 4: ...se respect without fail the following Do not place in an explosive area Necessary repairs maintenance and cleaning in particular in the field of electrical equipment may only be realized by qualified...

Страница 5: ...haust side Attach the transport lid at the sucking side and if used filters are installed seal additionally with tape 4 Scope of delivery at purchase and rental 4 1 Scope of delivery The delivery of t...

Страница 6: ...negative pressure An integrated filtering system establishes the conditions that the asbestos concentration in the exhausted air does not exceed max 1000f m The exhausted air is blown in the open air...

Страница 7: ...hetic Degree of separation Am 90 Nominal rated current 5400 m h m Nominal velocity in blower stream by nominal volume 1 5 m s Difference of initial pressure 42 Pa Recommended final pressure drop 250 P...

Страница 8: ...RF relative humidity Filter area 2 3 m Filter dimensions 592 x 592 x 330 mm 5 4 3 Main filter Frame Plastic Filter medium Glass fibre Sealing compound Polyurethan Seal Polyurethan foamed Filter area...

Страница 9: ...mportant Use only authorised faultless filter With filter in new state approximately 650 Pascal are displayed on the gauge Evaluated at 100 capacity We recommend a filter change at about 1300 Pascal i...

Страница 10: ...ance of 15 based on the measuring range end value determined in a multi point measuring method with a calibrated vane anemometer 6 1 Fan guide line 0 500 1000 1500 2000 2500 3000 5000 8000 10000 15000...

Страница 11: ...or Power 18 5 KW 6 3 Filter system 3 stage Pre filter EU 4 610 x 610 x 47 mm Bag filter F5 592 x 592 x 360 mm HEPA Filter pursuant EN 1822 Class H13 610 x 610 x 292 mm 6 4 Connections Dimensions Weigh...

Страница 12: ...ot operate unit if it is visibly damaged Please inform deconta GmbH immediately Connect the container to the sanitation area Seal the container with the sanitation area Ensure that sufficient fresh ai...

Страница 13: ...es permanently via a measuring tube the actual negative pressure in the sanitation area and controls according to its specifications the Negative Pressure Unit automatically The requested negative pre...

Страница 14: ...ration the set value for the negative pressure in Pascal is entered with the buttons and display set value in automatic operation By comparing the entered set value with the permanently measured actua...

Страница 15: ...40sec 8 2 Version with SE control The negative pressure unit is as standard supplied with a manual infinitely variable control The desired negative pressure is set via the manual power control and or...

Страница 16: ...ing the operation the filter state has to be controlled as described under 5 5 9 3 Filter change Attention Contaminated filters have to be changed under all corresponding safety measures see TRGS 519...

Страница 17: ...card Check and clean the sealing surfaces on the unit Insert the new HEPA filter Reattach clamping bar Attach Pre and bag filter frame and insert filter Important Main filters must be handled with car...

Страница 18: ...filtration To install a second main filter level double filtration proceed as follows Remove Pre and Bag filter Unscrew clamping bolts of Pre and Bag filter frame and remove whole frame Loosen nuts an...

Страница 19: ...ual Compact 25 000 Seite 19 Remove screws of clamping device Attach extensions to the Clamping device and bolt together the extensions are at the side walls Screws Clamping device Extension Mounting w...

Страница 20: ...struction manual Compact 25 000 Seite 20 Insert two main filters one behind the other Fasten clamping bar Fix Pre and Bag filter frame and insert filters Clamping bar 1 Main filtration 2 Main filtrati...

Страница 21: ...Instruction manual Compact 25 000 Seite 21 11 Circuit diagram 11 1 Version SRE Type 524...

Страница 22: ...Instruction manual Compact 25 000 Seite 22 11 2 Version SE Type 532...

Страница 23: ...Instruction manual Compact 25 000 Seite 23 12 Sound level measuring Value in dB A Status Engine power 100 free discharge outside...

Страница 24: ...20 D 46419 Isselburg Product Negative pressure unit Type 524 532 The design of the unit complies EU Machine directive 2006 42 EG with the following directives EU Low voltage directive 2006 95 EG Appli...