Installation Instructions

 

Version 0.2 

27/09/2016 

page 5 of 13 

 

2. 

Fire detectors  

2.1. 

Sensor and base 

Certain fire detectors always consist of a base and a sensor. The conventional sensors SLR-E3, FJ-
AE3, DFJ-CE3, DCD-AE3 and DCD-CE3 can all be mounted on the standard base (YBN-R/6). Follow 
the guideline given below to install and maintain the FMS.  

In case these instructions are ignored, correct functioning cannot be guaranteed!

 

Warning: 

The CDX range of sensors cannot be used to prevent fires, but are rather only intended to detect a 
certain characteristic of a fire.  

The sensors DCD-AE3 and DCD-CE3 are used to detect changes of temperature and cannot detect 
smoke or other phenomena. When installing sensors, check that the location of each individual sensor 
complies with the applicable regulations and recommendations. 

2.2. 

Connection of different fire detector types 

Each fire loop module (FM) has eight conventional loops. After installation, all connections are to be 
secured with screws to prevent them coming loose due to vibration. The drawing shows a connection 
plan of various conventional sensor and base types to a fire loop module (FM).  

Содержание FMS3000

Страница 1: ...6 page 1 of 13 Fire Alarm System FMS3000 Installation Instructions Version history Version Date Author Checked Note 0 1 16 09 13 JB TK Produced based on the old operating instructions 0 2 27 09 16 TK STO Configuration update explained in more detail page 13 Checked by ES Elektronik Service Jan Broockmann 23 09 2013 Name company Date Approved by Thomas Kruse DECKMA GMBH 23 09 2013 Name company Datu...

Страница 2: ... 5 2 3 Guideline for the installation of sensors and bases or fire detectors 7 2 4 Testing the fire detectors 7 3 Commissioning 8 3 1 General 8 3 2 Outputs 8 3 3 Setting the BUS address 9 3 4 Termination resistors 9 3 5 Use of the modules components 9 3 6 Organisation of the software versions 10 3 7 Sequence of on board commissioning 10 4 Maintenance 10 4 1 Checking the fire detectors 10 4 2 Check...

Страница 3: ...module if present VDR and printer module output the fire alarm through a VDR output or through the printer In addition the main module informs the main panel HT about the fire alarm and it then warns the user acoustically and optically of a fire 1 Cabling requirements For safe operation of the entire system the following cables are recommended Plug Module Cable type Wires diameter POWER Main JN0 M...

Страница 4: ...6 VDR RS 232 JP3 VDR module shielded standard serial cable PRINTER JR1 printer module shielded standard parallel printer cable The recommended cable types are FMGSGO LMGSGO and MGSGO Marine according to VG95218 Part 62 1 Cross section according to length of cable and current 2 Number of wires depends on the outputs to be connected 3 Cross section depending on the length of the loop 4 Number of wir...

Страница 5: ...unctioning cannot be guaranteed Warning The CDX range of sensors cannot be used to prevent fires but are rather only intended to detect a certain characteristic of a fire The sensors DCD AE3 and DCD CE3 are used to detect changes of temperature and cannot detect smoke or other phenomena When installing sensors check that the location of each individual sensor complies with the applicable regulatio...

Страница 6: ...cal documentation 201309IA FMS3000 Tel 49 0 4105 65 60 0 DECKMA GmbH Fax 49 0 4105 65 60 25 Email info deckma gmbh de Internet www deckma gmbh de Installation Instructions Version 0 2 27 09 2016 page 6 of 13 ...

Страница 7: ... the sensor or the base Certain actions can lead to permanent damage to the sensor o Dismantling the housing o Impacts or shocks 2 4 Testing the fire detectors If damage to a fire detector is suspected it is to be replaced After installation all fire detectors in the fire alarm system are to be tested to ensure that all function correctly Installation and maintenance should only be carried out by ...

Страница 8: ...s 3 2 Outputs The standard assignment of the outputs of the output module must be Machine alarm system fire alarm faults General alarm VDR Fault and common status display The remaining outputs can be freely configured If these outputs are not configured the MED permit for the FMS immediately becomes invalid The relay outputs output module JR1 JR2 fire module FM JAN JAP in the output module and the...

Страница 9: ...r between Pin 6 and Pin 14 Parallel operation 2 jumper between Pin 7 and Pin 15 In addition a termination resistor 120 Ohm must be inserted in the last main panel in the FMS BUS directly in the D SUB connector between Pin 12 and Pin 4 Even when only one main panel is being used a termination resistor is to be inserted If more than one identical BUS addresses are present in an FMS BUS this causes s...

Страница 10: ... Checking fire detectors The functioning of fire detectors is to be checked at yearly intervals Dirty and defective detectors are to be replaced immediately Defective of missing detectors cause a fault report 4 2 Checking and changing the accumulator The average lifetime of the accumulator is about 4 5 years at an ambient temperature of 25 C The accumulators should therefore be replaced as a preca...

Страница 11: ... depth 53mm plus the corresponding D SUB connector 5 2 Switch cabinet installation The switch cabinet which houses the power supply the main module the power supply the printer module the VDR module the fire loop module FM the output module and the accumulator is usually installed inside the control console on the command bridge and connected to the operating panel with a plugged cable connection ...

Страница 12: ...beleinführung Seitenansicht Kabeleinführung Befestigungsabmessungen 350 Draufsicht Anordnung Module 345 350 Seitenansicht Material Stahlblech 1 5mm Montageplatte Stahlblech 3mm Lackierung Grau RAL 7035 Deckelbefestigung mittels 4 Schrauben M6 Mounting Measurement 530 500 295 350 Netzteilkarte Kundenkabelkanal Ausgangskarte Feuermeldekarte Feuermeldekarte Feuermeldekarte Loop 1 8 Loop 9 16 Loop 17 ...

Страница 13: ...rted into the data module In order to load this configuration file into the FMS the data module is plugged into JR2 main module while it is switched off When the FMS is switched on the configuration file is automatically loaded LEDs inside the data module will indicate this loading process When the loading process has been completed the LEDs will stop flashing the FMS restarts automatically After ...

Отзывы: