De Dietrich Thermique EFU 22 Скачать руководство пользователя страница 1

BE - ER15012

1 / 5

IT2656

Technical Sales 

Documentation Department

TI

Technical information

Heading No 1

Fuel oil fired boilers

EFU 22 / 29 (FF) - EFU C 19 / 24 / 32

EFU C 24 /32 PLUS

Diagnostic aid - Fault finding

Product evolution

P5253 JS F 67580 Mertzwiller

N° IT2656

-en

27/01/2017

EN

1. Blocking of the safety control box

After 5 safety shutdowns, the safety box remains blocked at fault. 
To unlock the safety box: turn off the burner power supply with the ON/
OFF button or by pulling out the burner plug. 
After switching on again, reset the safety box by pressing the reset button.

The fault counting of the safety box is reset to 0, after each safety 
box switching off (switching off by 

ON/OFF

 button, by unplugging 

the burner or by power failure). 

Troubleshooting help

 - Signification of the safety control box reset 

button flashing:

L000836-A

Normal operating

Reset button colour

Seconds

Colour code

OFF

OFF

-

-

-

Pre-heating time

GREEN blinking

0,5

2,5

Pre-ventilation

ORANGE blinking

0,5

0,5

Safety time

GREEN blinking

0,5

0,5

Normal operating

GREEN

*

-

-

Blinking

or steady ON

Fault description

Reset button colour

Seconds

Colour code

Extraneous light (false flame signal)

GREEN

, RED

blinking 

alternately

0,5

0,5

Frequency supply error

OR

A

NGE

-

-

Steady ON

Voltage monitor error

OR

A

NGE, 

GREEN

fast 

blinking alternately

0,2

0,2

Reset button fault

GREEN

, RED fast 

blinking 

alternately

0,2

0,2

Lockout due to no flame after ts

RED

-

-

Steady ON

Lockout for false flame signal

RED

blinking

0,5

0,5

Lockout for maximum number of recycles

RED

fast blinking

0,2

0,2

Lockout for pre-heating not finished

RED blinking

0,5

2,5

Lockout for fan motor error

RED, OR

A

NGE

inverted blinking

2,5

0,5

Lockout for oil valve error RED

RED, GREEN

inverted blinking

2,5

0,5

Lockout for eeprom error

OR

A

NGE, GREEN

blinking alternately

0,5

0,5

Key :
ON

OFF

Colour code

RED

ORANGE

GREEN

* Blinking depending on the flame signal quality : correct (1-2 blinks), 
good (3-4 blinks) or excellent (5 blinks or always ON). 