P4
P3
HY1
DE1
ROP
AL1
AL2
AL3
AL4
AC1
AC2
AC3
AC4
HY2
HY3
HY4
SB
SDT
DOP
HI
DE2
DE3
DE4
HI
HI
0000
0000
0000
0000
0000
00
POL
AOP
ANL
ANH
00
00
0000
9999
ADD
BAU
PAR
FRA
0000
NO
NO
384
n.8.2.
ADJ
DOF
DGA
AOF
0000
0000
AGA
0000
0000
IO
-IO
DO
-DO
ADE
E00
**Please check the wiring connection is correct first, if the problem still exist, please return the meter
Error Code of Self-Diagnosis
to the factory.
Descriptions
Display
EEPROM reading/writing suffers the interference (about 1 million times).
Input signal is under -20% of input range.
Input signal is over 120% of input range.
Input signal is over 180% of input range or meter error.
Input signal is under display range (-19999)
Input signal is over display range (99999)
Descriptions
Display
Default
RS485 Setting
Address Setting
Baud Rate
Parity Setting
Page (doP)
(Addr)
Setting (bAUd)
(PAri)
to modify address (0~255).
to select baud rate (38400/19200/9600/4800).
to select parity (n.8.2/n.8.1/even/odd).
RS485 Setting Group Procedures
(FrAmE)
Frame Setting
to select frame type.
( NO:Hi Lo , YES:Lo Hi )
Press
Press
Press
Press
The following steps are only available for RS-485.
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
A/O Setting Group Procedures
A/O Setting Page
(AoP)
The following steps are only available for analog output.
A/O Hi Scale
A/O Low Scale
Setting (AnLo)
Setting (AnHi)
A/O Polarity
Setting (PoLAr)
to select output for positive or negative pole.
to adjust A/O hi scale to correspond to
EX : A/O is 0~10V, the display is 10.0 to output 0V, this value must be set for 10.0.
the display value (programmable).
to adjust A/O low scale to correspond to
the display value (programmable).
EX : A/O is 0~10V, the display is 90.0 to output1 0V, this value must be set for 90.0.
PS : Voltage output ,NO: positive pole output (0~+10V)
YES: positive & negative pole output (-10~+10V)
Press
Press
Press
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Input / Output Adjustment Procedures
Display Offset
Setting (doF)
A/O Offset
Setting (AoF)
to display offset value (-1999~9999).
Press
to analog output offset value (-1999~9999).
Press
to analog output gain value (-1999~9999).
Press
A/O Gain
Setting (AGA)
to display gain value (-1999~9999).
Press
Display Gain
Setting (dGA)
Alarm Start Band
Setting (Sb)
to modify the value (-99~+99), if the display
value don't over this range; the alarm will not be act.
to modify the value (0~99 sec), if the display
after this value (sec).(The function is used with "Sb" function.)
value reach alarm start band value; the alarm will be act
Time Set ting (Sdt )
Alarm Start Band
Press
Press
S
e
tt
in
g
A
la
rm
R
un
D
el
ay
Delay Time 1
(dEL1)
(dEL2)
Delay Time 2
Delay Time 3
(dEL3)
(dEL4)
Delay Time 4
to modify the value, when the display value
(0~99 sec) for alarm action.
reach the alarm value that need to wait for this time
function will be disabled.
3. Press
ENT
to save the value and go to the next
PS: 1. There are 4 alarms output optional.
2. This page is exist without alarm output, but the
parameter.
Press
A
la
rm
H
ys
te
re
si
s
S
et
tin
g
to modify the value, when alarm runs
lower or higher display value (depends on alarm action).
function will be disabled.
3. Press
ENT
to save the value and go to the next
PS: 1. There are 4 alarms output optional.
2. This page is exist without alarm output, but the
parameter.
Press
+-
Alarm setpoint this range (0~999) will turn off the alarm.
Hysteresis 1
(HYS1)
(HYS2)
Hysteresis 2
Hysteresis 3
(HYS3)
(HYS4)
Hysteresis 4
S
e
tt
in
g
A
la
rm
A
c
ti
o
n
Alarm 3
Alarm 4
(ACt3)
(ACt4)
Alarm 1
Alarm 2
(ACt1)
(ACt2)
to modify alarm value that is
Press
(Hi)
or <(Lo) for alarm action.
>
=
to modify alarm value that is
Press
(Hi)
or <(Lo) or (Go) for alarm action.
>
=
to modify alarm value that is
Press
(Hi)
or <(Lo) or (Err) for alarm action.
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Press
ENT
Descriptions
Display
Default
The following steps are only available for alarm output.
Alarm Setting Group Procedures
Alarm Setting
Page (roP)
to modify alarm 1 setpoint.
Alarm 1
Setpoint (AL1)
Setpoint (AL2)
Alarm 2
to modify alarm 2 setpoint.
Setpoint (AL3)
Alarm 3
to modify alarm 3 setpoint.
Setpoint (AL4)
Alarm 4
Press
to modify alarm 4 setpoint.
Press
Press
Press