‘Lower’ functions either on a faceplate and/or a switch on input 1. Once
the system has been allowed to ‘time out’, light level will revert to the
default light level setting as above.

SWITCH INPUTS - OPERATION & DEFAULTS

The SET-DLCM3 and SET-DLCM5 have 5 x switch inputs which can be
used for various manual control options. There are also specific inputs
for ‘Emergency Test’ and ‘Override’. See ‘Inputs/Outputs And Status
LED’s’ on page 3 and the ‘Switch Functions Table’ below for further
details.

Switch 1:

 By default, this switch input is programmed to operate as ‘On’,

‘Off’, ‘Raise’ and ‘Lower’ using a momentary push switch.

Switch 2:

 Test Mode. A momentary switch wired to this input can be

used to activate ‘Test Mode’. The switch can be used to toggle between
on and off. With test mode on, the system will time out after occupancy
has ceased and switch lighting off after 10 seconds. A secondary
function of this switch is to allow you to invoke a ‘System Reboot’. Press
and hold the switch for more than 5 seconds then release. The device
will restart without losing any previously programmed settings.

Switch 3:

Programming Mode. A momentary switch wired to this input

will allow some quick and simple programming options to be selected. A
short press on this switch will toggle between DSI & DALI dimming
modes. A long press will store the currently selected scene’s output to
memory. Set your desired lighting output level by using the raise/lower
buttons on a faceplate or a switch wired to switch input 1. Store this level
with a long press on switch 3.

Another function of this switch is to enable a quick method of invoking a
‘Factory Reset’. Press and hold the switch for more than 5 seconds then
release. The device will reboot with all previously programmed settings
being cleared from memory.

Switch 4 & 5:

These switch inputs are not programmed on leaving the factory for any
particular function and can be programmed as required.

Switch 6: Emergency Test (E-TS):

 Input for standard ‘Keyswitches’ to

allow emergency lighting to be tested. By default the normal lighting will
turn off whilst discharging the emergency lighting. (Can be programmed
to keep the normal lighting on whilst discharging the emergency lighting)
This function affects all ‘Output’ devices on the same network.

Switch 7: Override (O-RD):

 By default this input is programmed to allow

for a complete system override either from a switch or volt-free contact.
On operation, the lights will go to full output with all inputs from any input
devices or sensors being ignored. May be used for interfacing with alarm
or BMS systems etc.

MODES OF OPERATION

The following table describes some basic ‘Modes Of Operation’
based on types of input, such as occupancy sensors, light level
sensors, switches and faceplates.

All methods connect to the RS485 network, either by direct connect-
ion at a specific device or through a SET-DPP (Daylux Programming
Port). The SET-DHPP also has the ability to use an IR (Infra-Red)
Link as a means of connecting to the network. Please see the
‘SET-DPP User Guide’, the ‘SET-DFP User Guide’, the ‘SET-DHHP
User Guide’ and the ‘SET-DPCS User Guide’ for further information
and programming instructions. Please contact Setsquare for any
programming requirements. (Contact details on back page).

Once the systems have been commissioned, the default settings
most likely would have been changed to specific requirements for the
site. If Setsquare undertake the commissioning, these settings are
recorded in an engineer’s report which is issued in the handover
documentation for the project.

CHANGING DEFAULTS SETTINGS - PROGRAMMING

The SET-DLCM is part of the DLCS range of products which are fully
networkable and programmable. It is possible to change any of the
default settings (program) for time delay, automatic light level,
dimming protocol change between DSI and DALI (SET-DLCM3-D
& SET-DLCM5-D only), manual scene levels and associated channel
selection, occupancy inputs and associated channels, switch input
configuration, network commands (such as corridor hold, group
control and interaction between devices).

There are various methods which can be used to program the
SET-DLCM. These are:- SET-DFP (faceplates), a SET-DHHP
(Daylux Hand Held Programmer) and the SET-DPCS (Daylux PC
Software).

The method used will determine what level of programming can be
achieved. The SET-DFP is the most basic means of programming
and the SET-DPCS is the most advanced.

MIN

MAX

MANUAL (ON OFF)

PRESENCE

ABSENCE

DAYLIGHT

DAYLIGHT / PRESENCE

DAYLIGHT / ABSENCE

DAYLIGHT / PRESENCE / DIMMING

DAYLIGHT / PRESENCE / SCENES /
DIMMING

MIN

MAX

KEY:

Daylight Link

Switch

Absence

Dimming

Scenes / Faceplate

Presence

MIN

MAX

Notes:

 A ‘short press’ is less than half a second. ‘Press and hold’ is for

longer than half a second. *Raise and Lower will only function when
dimmable lighting is being controlled.

SWITCH FUNCTIONS TABLE

SHORT
PRESS

SW1

SW2

SW3

SW7

LIGHTS

ON

LIGHTS

OFF

SHORT
PRESS

PRESS

HOLD

PRESS

HOLD

INCREASE

LEVEL*

DECREASE

LEVEL*

TEST

ON

TEST

OFF

OVERRIDE

ON

OVERRIDE

OFF

SW6

EM TEST

ON

EM TEST

OFF

For >5s

RESTART

DSI/DALI
TOGGLE

>0.5s

STORE
SCENE

>5s

FACTORY

DEFAULTS

Содержание SET-DLCM3,5 (A,D)

Страница 1: ...ease note ALL commands and triggers from faceplates or switches are broadcast across the network and ALL output devices will respond 3 or 5 Channel control and lighting distribution 10 x Outputs to luminaries using industry standard Wieland connectors Capable of Dimming and or Switching from one unit All common dimming protocols supported DSI DALI Broadcast and 1 10v Analogue Automatic light level...

Страница 2: ...l go to full output with all inputs from any input devices or sensors being ignored May be used for interfacing with alarm or BMS systems etc MODES OF OPERATION The following table describes some basic Modes Of Operation based on types of input such as occupancy sensors light level sensors switches and faceplates All methods connect to the RS485 network either by direct connect ion at a specific d...

Страница 3: ...ü ü ü ü ü ü ü ü ü ü ü ü 1 2 3 SET DLCM3 1 2 3 1 2 3 1 2 3 Lighting Outputs The SET DLCM3 has 4 x outputs for channel 1 4 x for channel 2 and 2 for channel 3 The SET DLCM5 has 2 x outputs per channel DLCS NETWORK AREA TERM SET DLCM3 HB SP1 SP2 www setsquare com 44 0 1732 851888 F CHANNEL 3 SW2 SW3 GND SW4 SW5 GND E TS GND O RD GND SWITCHES LOCAL SUPPLY SW1 GND CHANNEL 2 E CHANNEL 1 SENSOR INPUTS C ...

Страница 4: ...nication data between devices connected to it Addressable Each device connected to a network has a unique address which enables communication directly to that device LED Light Emitting Diode PSU Power Supply Unit Daylight Linking Ambient light level Lux is monitored by the means of a sensor If the Lux level is above a preset level lighting output will be decreased to save energy and to maintain a ...

Отзывы: