Page 6  

AC Power Connections 

 

 
Connect the device to be powered ON and OFF to the IEC receptacle 
marked 

Switched Outlet

. A short IEC 320 to North American (NEMA 5-15) 

power cord is included for connecting the iBoot outlet to the device to be 
power controlled.   
 
If a cord with a different terminating recepticle is required, be sure it is 
properly rated and meets all the required local electrical standards.   If the 
device to be powered uses an IEC320 receipicle and detachable power cord, 
an IEC to IEC extension cord can be used. 
 
The iBoot can be connected to a power strip to allow simultaneous control of 
multiple devices. 
 
Make sure that the combined load of all controlled devices does not exceed 
12 Amps for 105-125VAC or 10  Amps for 210-240VAC. 
 
An LED Indicator next to the Switched Outlet will be On to indicate that the 
power is On at that outlet.  This LED will turn Off to indicate that the power to 
the switched outlet is Off. 
 

Switched
Outlet On

Connect Device to be Powered to iBoot

Use either:
IEC to NEMA Extension Cord 
  (supplied)
      -  OR  -
IEC to your country specific 
outlet (not supplied)
      -  OR  -
IEC to IEC Extension Cord
   (not supplied)

IEC to IEC
Extension Cord

Switched
Outlet On

IEC to NEMA
Extension Cord

Power Controlled Device

105-125 VAC 12A
210-240 VAC 10A

105-125 VAC 12A
210-240 VAC 10A

Содержание IBOOT -

Страница 1: ...s Using ibootrst exe Using ARP Ping Web Browser Operation 11 Password Protection Control Status Page iBoot Setup 13 Device Settings TCP IP Settings Auto Ping Heartbeat Passwords Forgotten Password Adv...

Страница 2: ...prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this prod...

Страница 3: ...built in hub make installation of iBoot easy Uses for iBoot Remote reboot of any device routers servers kiosks etc The device to be rebooted need not be network attached Secure sensitive devices by ke...

Страница 4: ...this feature uses a periodic message sent to the iBoot from a device When that message is not received the iBoot will perform the programmed power control function iBoot Control Programs Dataprobe of...

Страница 5: ...m the wiring closet to be used for both iBoot and the device it is powering or any other device This greatly simplifies installation Use of both network jacks is optional Note iBoot supports DHCP If y...

Страница 6: ...can be connected to a power strip to allow simultaneous control of multiple devices Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105 125VAC or 10 Amps for 210...

Страница 7: ...r end to your AC source If a power cord with a different terminating plug is required be sure it is properly rated and meets all the required local electrical standards Uplink Downlink A C Input Conne...

Страница 8: ...ll as Subnet Mask and Gateway to the iBoot If you power up iBoot without a fixed static IP address the DHCP server will be able to assign an IP address This is the factory default setting for iBoot On...

Страница 9: ...probe com power iboottools html To use ibootrst exe the computer running the program must be on the same subnet and network segment as the iBoot is to be programmed to Same subnet can be directly conn...

Страница 10: ...the iBoot and the MAC address is the MAC Address of the iBoot The MAC Address of the iBoot is located on bottom of the unit Example arp s 63 211 86 165 00 50 c2 05 01 c1 enter new IP addr MAC addr 3 P...

Страница 11: ...e methods described enter that address otherwise use the default IP address 192 168 1 254 Enter the default password PASS or your password if it has been changed A Username is not required When the pr...

Страница 12: ...escribed in greater detail in the Advanced Operation section on page 16 Use the Refresh link to obtain the latest status of iBoot Using your browser s refresh button can lead to inadvertent power swit...

Страница 13: ...nter either a new IP address or address 0 0 0 0 to enable Automatic IP addressing via DHCP Once you click Apply for this section also click the Reboot button that will appear at the top of the page Th...

Страница 14: ...ion for Auto Ping Setup Heartbeat Setup See Advanced Operation for Heartbeat Setup Power and System Passwords Two passwords are provided The Power Password allows access to the control of iBoot but no...

Страница 15: ...d use ibootrst exe All iBoot tools are available at www dataprobe com power iboottools html For security purposes you will need to power up the iBoot and complete the reset to factory defaults within...

Страница 16: ...monitored and reboot it automatically when it no longer responds Use Auto Ping Remotely Put iBoot at a central facility to monitor a remote system and power up an alert when the remote device no long...

Страница 17: ...ng response iBoot will power off When the ping response returns iBoot will power on Power Cycle Upon loss of ping response iBoot will cycle the power iBoot will wait the Ping Frequency if the response...

Страница 18: ...that will run as a tray applet that will transmit either continuous heartbeats to an iboot A Windows dll file is also available for use by Windows applications A Windows executable that will run as a...

Страница 19: ...wer on When the heartbeat returns iBoot will power off Power Off Latch Upon loss of heartbeat iBoot will power off and remain so until changed via the web ibootctl exe or direct messaging Power Off Fo...

Страница 20: ...rogram To begin use first click Setup Enter the IP address for the iBoot the Port configured for the Heartbeat in iBoot the frequency of heartbeats and a Fail Count This fail count does not affect the...

Страница 21: ...enter program allows control of multiple iBoot units This program provides the ideal means of monitoring and managing a large number of iBoots distributed throughout your organization Both programs ar...

Страница 22: ...m2 X3C Voltage Range Auto Sensing 105 240 VAC Switched Receptacle 3 Prong Female IEC Capacity 12 Amps Max at 105 125 VAC 10 Amps Max at 210 240 VAC Network Dual 10 100 Unshielded Twisted Pair Ethernet...

Страница 23: ...nical Service at 201 967 8788 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipmen...

Страница 24: ...functions be enabled User selectable security call processing and power control features are examples of such capabilities Visit www dataprobe com power ppal html Remote Power Control Console Port Ac...

Отзывы: