daviteq WS433-DI Скачать руководство пользователя страница 2

Input

2 channel Digital inputs with dry-contact or voltage input (max 3.3VDC)

Functions

M12-female, 4-pin A-coding

Electrical connection

Shielded cable 0.5m length with PG9 cable gland

Optional accessories

304SS Adapter PG9/male 1/2"NPT or PG13.5 or M20 to allow direct
mounting on Process instruments or electrical panel

Data speed

Up to 50kbps

Tranmission distance, LOS

500m

Antenna

Internal Antenna, 3 dBi

Battery

01 x AA 1.5VDC, up to 10-year operation, depends on configuration

Frequency Band

ISM 433Mhz, Sub-GHz technology from Texas Instrument, USA

Receiving Sensitivity

-110dBm at 50kbps

International Compliance

ETSI EN 300 220, EN 303 204 (Europe) FCC CFR47 Part15 (US), ARIB
STD-T108 (Japan)

Security Standard

AES-128

Operating temperature of PCB

-40oC..+60oC (with AA L91 Energizer)

Housing

Poly-carbonate, IP67

Installation method

L-type bracket SUS304 , by M4 screws or double-sided 3M tape
(included)

Product dimensions

125x30x30mm

Net weight (without battery)

< 100g

Box dimension

190x50x50mm

Gross weight

140g

4. Product Pictures

Содержание WS433-DI

Страница 1: ...by switch Change RF data rate by button Wireless sensor with 2 channel digital inputs to detect logic status 0 1 OR counting pulses from proximity sensor limit switch machine output pressure switch I...

Страница 2: ...tery 01 x AA 1 5VDC up to 10 year operation depends on configuration Frequency Band ISM 433Mhz Sub GHz technology from Texas Instrument USA Receiving Sensitivity 110dBm at 50kbps International Complia...

Страница 3: ......

Страница 4: ...d the analytic data of DI1 and DI2 Counter value Hour counter value DI1 and DI2 can work as a counter to count the Digital Pulse applied on them The recommended max frequency of Pulse is 1Hz The highe...

Страница 5: ...link for more information http filerun daviteq com wl id jhA8Bk46jtMORODSOuKfEwVajKEGeSPX You can configure the wireless sensor with the co ordinator by following the steps in the link below http www...

Страница 6: ...VCC to any external power source more than3 3VDC Note To change the Digital Input function toCounter uncover the housing find the Status switch and turn it to Counter take the battery out wait5 secon...

Страница 7: ...s for battery installation Using Philips screw driver to unscrew M2 screw at the side of housing Carefully pull out the top plastic housing in the vertical direction 7 4 Power Supply Battery installat...

Страница 8: ...ring it requires to have much pulling force at the beginning therefore please do it carefully to avoid the damage of circuit board which is very thin 1 00mm Insert the AA battery please take note the...

Страница 9: ...Insert the top plastic housing and locking by M2 screw...

Страница 10: ...correctly Reconfigure the RF data rate with the button according to the instructions Distributor in Malaysia AVO Technology Sdn Bhd Official Website www avo com my No 17 Jalan 3 23A Taman Danau Kota 5...

Отзывы: