After Zero and Span, you will get the voltage output correspond to zero gas and span gas value;

Enter these values into your reading device (PLC...) to get correct reading.

- Place the sensor in the area to monitor the target gas concentration. Please always check the gas molecular weight

v.s the air.

- For example, NH3 gas has a lighter weight than air, so the sensor must be placed at a height higher than the source

of NH3 leakage. Normally, the sensor will be mounted at a height of 1.6m from the ground.

Use the M12-Male cable Coding A, 4 pin as below picture. 

Because the Output is 0-10VDC, we do recommend to use the following cable for extention:

Cable size: minimum 24AWG (or minimum 0.5 mm2 core)

Cable type: Shielded

Max recommended cable legnth: 20m

Connect the wires to Reading device as below:

PWR+: 12-36VDC

PWR-: GND

OUT: 0-10VDC OUTPUT

NC: Not used

Step 3: Entering values to reading device

3. Installation

Notes:

* Avoid the place with humidity higher than 90% RH all the time (a short time in 2-3 days is acceptable)

* if the Sensor is intended to install outdoors, please use a rain guard to protect the sensor from rain and direct
sunlight. Please 

contact us

 to buy this accessory.